Review Details: ELECTRICAL

Permit Number - T07EL00318
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM00318 4/18/07

1. Provide a plan view with outline of property, street address, residence, and equipment.
2. Account for any new electrical loads added, this permit. If no electrical loads are to be added with this permit, state so on the plans.
3. Show tie-in to existing equipment on plans.
4. It appears that the Grounding Electrode Conductor needs to be sized at 1/0. Reference NEC 250.66.
5. Provide TEP available fault current, and fault current rating of new and existing equipment.