Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
6161 E PIMA ST
Apply Date:
08/08/2007
Applicant:
GARY STRIYLE
Description:
TI: REMODEL LEASING OFFICE
Architects:
  • SHINGLETON, GERALD LEE
Contractors:
  • MULTIFAMILY SERVICES BUILDING INC
  • PRAXIS CONSTRUCTION GROUP L L* C

Permit Reviews

Permit Number - T07CM03300
Permit Status: C of o
Permit Description: TI: REMODEL LEASING OFFICE
Start Date Submittal Complete Date Status  
04/22/2010 REVISION - - 1ST 04/22/2010 COMPLETED Review Details
08/08/2007 COMMERCIAL TI 08/09/2007 COMPLETED Review Details
08/09/2007 OTHER 08/09/2007 COMPLETED Review Details
08/09/2007 OTHER 08/10/2007 COMPLETED Review Details
08/11/2007 OTHER 03/04/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07CM03300
Permit Status: C of o
Permit Description: TI: REMODEL LEASING OFFICE
Total Outstanding Activity Conditions - 1
Date Name
08/08/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T07CM03300
Permit Description: TI: REMODEL LEASING OFFICE
Total Completed Inspections - 19
Date Description Inspector Results Comments
09/26/2007 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
09/27/2007 FRAMING JBURGE Approved IVRS - Inspection :*
CALL WHEN RESTROOM CHANGES ARE COMPLETED ON THE APPROVED PLANS
09/27/2007 NPPO - FINAL ACONNOR Approved N/A
09/27/2007 LANDSCAPE - FINAL ACONNOR Approved N/A
10/02/2007 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
OK WALLS
10/03/2007 SHEET ROCK NAILING JBURGE Approved IVRS - Inspection :*
OK TO SHEETROCK & TAPE ONE SIDE
10/18/2007 BUILDING - FINAL JBURGE Approved IVRS - Inspection :*
NEED ELECTRIC FINAL
10/18/2007 PLUMBING - FINAL RLEDONNE Approved IVRS - Inspection :*
10/18/2007 ENGINEERING - FINAL JBRUCKME Approved
10/18/2007 FIRE - FINAL LTHOMAS Approved
10/29/2007 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20
2. A MANUFACTURES HOLD IS NEEDED FOR BACK FED BREAKER - 408.16
3. CANNOT TRIM CONDUCTORS
4. FINISH #6 OF PREVIOUS INSPECTION - MAIN IS NOT 100 AMP AS PER PLANS.
03/26/2010 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
03/26/2010 MECHANICAL - FINAL JBURGE Approved IVRS - Inspection :*
03/26/2010 MECHANICAL - INTERMEDIATE JBURGE Approved IVRS - Inspection :*
03/26/2010 BUILDING - PROGRESS JBURGE Approved IVRS - Inspection :*
03/26/2010 RIGHT OF WAY - FINAL PWhiddon Approved
05/20/2010 PLUMBING - ROUGH, SOIL BBENEDON Approved IVRS - Inspection :*
06/02/2010 PLUMBING - INTERMEDIATE BBENEDON Approved IVRS - Inspection :*
06/03/2010 PLUMBING - PRE SLAB BBENEDON Approved IVRS - Inspection :*

Documents

File Name Document Type  
C OF O_06-07-2010.TIF CERT OF OCC VIEW
None DOCUMENTS VIEW
001_T-1.TIF CONSTRPLANS VIEW
002_ADA-1.TIF CONSTRPLANS VIEW
003_ADA-2.TIF CONSTRPLANS VIEW
004_A1-0.TIF CONSTRPLANS VIEW
005_A-2.0.TIF CONSTRPLANS VIEW
006_A-3.0.TIF CONSTRPLANS VIEW
007_M-1.TIF CONSTRPLANS VIEW
008_P-1.TIF CONSTRPLANS VIEW
009_P-2.TIF CONSTRPLANS VIEW
010_E-1.TIF CONSTRPLANS VIEW
011_E-2.TIF CONSTRPLANS VIEW
013_E-3.TIF CONSTRPLANS VIEW
001_X1.TIF CONSTRPLANS VIEW
002_A1.TIF CONSTRPLANS VIEW
003_P1.TIF CONSTRPLANS VIEW