Permit: T07CM03300

Parcel: 12101005A


Addresses:

6161 E PIMA ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM03300

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/19/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/14/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20
2. A MANUFACTURES HOLD IS NEEDED FOR BACK FED BREAKER - 408.16
3. CANNOT TRIM CONDUCTORS
4. FINISH #6 OF PREVIOUS INSPECTION - MAIN IS NOT 100 AMP AS PER PLANS.
10/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO POWER TO RECEPTACLES IN OFFICE
2. CONNECT EQUIPMENT GROUNDING CONDUCTOR TO SWITCHES.
3. EM/NL NOT PER PLAN
4. INSTALL BREAKERS LISTED FOR USE IN PANEL
5. PROVIDE DETAILED PANEL SCHEDULE
6. SEE SERIES RATING NOTE ON SHEET E-3 REQUIRES MAIN BREAKER TO BE REPLACED WITH 22K A/C RATING & ALL DOWNSTREAM BREAKERS TO BE 10 K A/C