Permit Number: T07CM03300
Parcel: 12101005A

Address:
6161 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03300
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2007 MARTIN BROWN FIRE REVIEW Approved
08/08/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/08/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03300 8/8/07

1. Electrical load on Ckt 12 is 2166VA, or 2707VA considering continuous loading. This would put 23A on a 20A circuit.
2. Panel appears overloaded. Reference NEC 220.87.
08/08/2007 ROBERT SHERRY WATER REVIEW Approved
08/08/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
08/08/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/09/2007 GBONILL1 WWM REVIEW Needs Review
08/09/2007 TERRY STEVENS ZONING REVIEW Approved
08/09/2007 ANY ENGINEERING REVIEW Approved
08/09/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review