Permit Reviews

Permit Number - T06CM05260
Permit Status: Expired
Permit Description: TI:PRECISION MACHINING SHEETMETAL
Start Date Submittal Complete Date Status  
10/04/2006 COMMERCIAL TI 10/05/2006 COMPLETED Review Details
10/05/2006 COMMERCIAL TI 04/13/2007 COMPLETED Review Details
11/17/2008 REVISION - - 1ST 11/17/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM05260
Permit Status: Expired
Permit Description: TI:PRECISION MACHINING SHEETMETAL
Total Outstanding Activity Conditions - 1
Date Name
10/04/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Expired
Permit Number: T06CM05260
Permit Description: TI:PRECISION MACHINING SHEETMETAL
Total Completed Inspections - 15
Date Description Inspector Results Comments
10/24/2007 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
OFFICE NEXT TO INSPECTION ROOM
CHANGE FRAMING TO PARTIAL
11/15/2007 PLUMBING - ABOVE CEILING BBENEDON Approved IVRS - Inspection :
See detailed listing on site.| 999*
11/15/2007 ELECTRIC - ABOVE CEILING CCLEMENS Approved IVRS - Inspection :*
12/13/2007 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE 1" DUCT LINER PER GENERAL NOTE 3
15400 PARAGRAPH 5 - INSULATE CONDENSATE PIPING IN WALLS AND ABOVE CEILINGS
12/14/2007 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
1. ABS THRU ROOF OK
INSTALLED PER REDLINE
WATER TEST OK
2. COPPER INSTALLED PER REDLINES. YARD WATER PER REDLINE
3. NEED TO SEE FLANGES SCREWED DOWN
12/14/2007 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
SEE NOTE NUMBER 2 FROM 11/15/07
WATER NOT PER PLAN - OUTSIDE YARDWATER REQUIRED MINIMUM 12" COVER AT ALL POINTS. ALL FITTINGS AND CONNECTIONS TO BE EXPOSED. ALL PIPING WITHIN 1 1/4" OF THE STUD FACE TO BE PROTECTED.
12/21/2007 FRAMING AQUIROZ Approved IVRS - Inspection :*
1) EXCLUDES RESTROOMS MISSING BLOCKING FOR ADA
12/21/2007 ELECTRIC - INTERMEDIATE CCLEMENS Approved IVRS - Inspection :*
1) NEED TO FINISH ALL PREVIOUS CORRECTION 3 WAY NOT MADE UP CORRECTLY, WHERE IS OTHER SWITCH FOR 3 WAY ?
10/24/2008 MECHANICAL - FINAL MRAMBER Approved
10/24/2008 ELECTRIC - FINAL RHOLLAND Approved 1. INSTALL CONDUCTOR FULLY UNDER TERMINAL SCREWS ON DEVICES
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
3. PLEASE VERIFY LISTING AND LABELING OF EQUIPMENT
4. MISSING EM & EXIT LIGHTS AS PER PLAN
5. NEED PANEL DIRECTORY AS PER 408.4 ALSO, LABEL OUTSIDE COVER
6. ELECTRIC FROM SERVICE TO PANEL AS PER CODE
7. SUPPORT CONDUIT TO PANEL AS PER CODE
8. SWITCHING NOT AS PER PLANS
9. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN EQUIPMENT AND LIGHT TO INSPECT
10/24/2008 BUILDING - FINAL GDABBS Approved IVRS - Inspection :*
NEED TO FINAL ELEC, MECH, PLUMBING FINALS AND
FIRE C OF O BEFORE BUILDING FINAL
10/24/2008 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*
10/24/2008 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection :*
11/19/2008 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
03/26/2009 FIRE - FINAL LTHOMAS Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW
5260-01-0001-01-ORIGINAL001.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL002.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL003.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL004.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL005.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL006.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL007.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL008.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL009.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL010.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL011.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL012.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL013.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL014.TIF CONSTRPLANS VIEW
5260-01-0001-01-ORIGINAL015.TIF CONSTRPLANS VIEW