Permit: T06CM05260
Permit Details
Apply Date:
10/04/2006
Applicant:
N/A
Description:
TI:PRECISION MACHINING SHEETMETAL
Architects:
- HARRINGTON, JAMES EDGAR
Contractors:
- ALEGRE BUILDERS
Permit Reviews
Permit Number - T06CM05260
Permit Status: Expired
Permit Description: TI:PRECISION MACHINING SHEETMETAL
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
10/04/2006 | COMMERCIAL TI | 10/05/2006 | COMPLETED |
10/05/2006 | COMMERCIAL TI | 04/13/2007 | COMPLETED |
11/17/2008 | REVISION - - 1ST | 11/17/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM05260
Permit Status: Expired
Permit Description: TI:PRECISION MACHINING SHEETMETAL
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
10/04/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Expired
Permit Number: T06CM05260
Permit Description: TI:PRECISION MACHINING SHEETMETAL
Total Completed Inspections - 15
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/24/2007 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* OFFICE NEXT TO INSPECTION ROOM CHANGE FRAMING TO PARTIAL |
11/15/2007 | PLUMBING - ABOVE CEILING | BBENEDON | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
11/15/2007 | ELECTRIC - ABOVE CEILING | CCLEMENS | Approved | IVRS - Inspection :* |
12/13/2007 | MECHANICAL - ABOVE CEILING | MRAMBER | Approved | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE 1" DUCT LINER PER GENERAL NOTE 3 15400 PARAGRAPH 5 - INSULATE CONDENSATE PIPING IN WALLS AND ABOVE CEILINGS |
12/14/2007 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* 1. ABS THRU ROOF OK INSTALLED PER REDLINE WATER TEST OK 2. COPPER INSTALLED PER REDLINES. YARD WATER PER REDLINE 3. NEED TO SEE FLANGES SCREWED DOWN |
12/14/2007 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* SEE NOTE NUMBER 2 FROM 11/15/07 WATER NOT PER PLAN - OUTSIDE YARDWATER REQUIRED MINIMUM 12" COVER AT ALL POINTS. ALL FITTINGS AND CONNECTIONS TO BE EXPOSED. ALL PIPING WITHIN 1 1/4" OF THE STUD FACE TO BE PROTECTED. |
12/21/2007 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* 1) EXCLUDES RESTROOMS MISSING BLOCKING FOR ADA |
12/21/2007 | ELECTRIC - INTERMEDIATE | CCLEMENS | Approved | IVRS - Inspection :* 1) NEED TO FINISH ALL PREVIOUS CORRECTION 3 WAY NOT MADE UP CORRECTLY, WHERE IS OTHER SWITCH FOR 3 WAY ? |
10/24/2008 | MECHANICAL - FINAL | MRAMBER | Approved | |
10/24/2008 | ELECTRIC - FINAL | RHOLLAND | Approved | 1. INSTALL CONDUCTOR FULLY UNDER TERMINAL SCREWS ON DEVICES 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 3. PLEASE VERIFY LISTING AND LABELING OF EQUIPMENT 4. MISSING EM & EXIT LIGHTS AS PER PLAN 5. NEED PANEL DIRECTORY AS PER 408.4 ALSO, LABEL OUTSIDE COVER 6. ELECTRIC FROM SERVICE TO PANEL AS PER CODE 7. SUPPORT CONDUIT TO PANEL AS PER CODE 8. SWITCHING NOT AS PER PLANS 9. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN EQUIPMENT AND LIGHT TO INSPECT |
10/24/2008 | BUILDING - FINAL | GDABBS | Approved | IVRS - Inspection :* NEED TO FINAL ELEC, MECH, PLUMBING FINALS AND FIRE C OF O BEFORE BUILDING FINAL |
10/24/2008 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :* |
10/24/2008 | PLUMBING - PROGRESS | RMYERS | Approved | IVRS - Inspection :* |
11/19/2008 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* |
03/26/2009 | FIRE - FINAL | LTHOMAS | Approved |