Permit: T06CM05260

Parcel: 11516028E

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM05260

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/16/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/10/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1 BREAKER TO BE FOR USE WITH
MANUFACTURES PANEL - 100A
2. STRAP CONDUIT 3' OF PANEL
3. EM AND EXIT LIGHTS TO BE AS PER PLANS AND 700.12(F)
4. BOXES MORE THAN 1/4" -- 314.20

*RECEIVED LETTER FOR PANEL AND FEEDER
02/05/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
MET WITH ELECTRICIAN TO DISCUSS JOB
01/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL, CEILING COVER
12/21/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) NEED TO FINISH ALL PREVIOUS CORRECTION 3 WAY NOT MADE UP CORRECTLY, WHERE IS OTHER SWITCH FOR 3 WAY ?
12/14/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROPERLY GROUND ALL BOXES AND TIGHTEN GROUND SCREWS
2. FINISH LOW VOLTAGE WIRING
3. IDENTIFY WHITE USED AS HOT IN SWITCH LEGS
4. GROUND NOT TO BE USED AS HOT FOR 3-WAYS -
USE 3 WIRE MC/CHECK MAKEUP
5. NAIL PLATES ARE NEEDED WHERE HOLE IS 1 1/4" OR LESS FROM STUD FACE
6. REMOVE UNUSED/ABANDONED WIRING BACK TO ITS SOURCE
11/15/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/04/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL A GROUND TAIL IN EACH 45 BOX ON BACK TO BACK BOXES.
2. WALLS PARTIAL - APPROVAL FOR ROUGH IS SUBJECT TO ARCH. APPROVAL FOR USE OF MC CABLE IN LIEU OF CONDUIT.
3. OK CEILING ROUGH SUBJECT TO NOTE #2
PROVIDE LETTER FOR USE OF MC FROM ARCH.