Permit: T06CM05260

Parcel: 11516028E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05260

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/16/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/10/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
02/05/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/24/2008 ELECTRIC - FINAL Not ready for Inspection 1. INSTALL CONDUCTOR FULLY UNDER TERMINAL SCREWS ON DEVICES
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
3. PLEASE VERIFY LISTING AND LABELING OF EQUIPMENT
4. MISSING EM & EXIT LIGHTS AS PER PLAN
5. NEED PANEL DIRECTORY AS PER 408.4 ALSO, LABEL OUTSIDE COVER
6. ELECTRIC FROM SERVICE TO PANEL AS PER CODE
7. SUPPORT CONDUIT TO PANEL AS PER CODE
8. SWITCHING NOT AS PER PLANS
9. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN EQUIPMENT AND LIGHT TO INSPECT