Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address NEW:
2200 N WILMOT RD #100
Apply Date:
07/20/2006
Applicant:
CARHUFF, PHILIP ANDREW
Description:
TI: OFFICE PRINT SHOP

Permit Reviews

Permit Number - T06CM04256
Permit Status: C of o
Permit Description: TI: OFFICE PRINT SHOP
Start Date Submittal Complete Date Status  
07/20/2006 COMMERCIAL TI 08/08/2006 COMPLETED Review Details
08/08/2006 OTHER 08/14/2006 COMPLETED Review Details
11/08/2006 REVISION - - 1ST 11/21/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM04256
Permit Status: C of o
Permit Description: TI: OFFICE PRINT SHOP
Total Outstanding Activity Conditions - 1
Date Name
07/20/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T06CM04256
Permit Description: TI: OFFICE PRINT SHOP
Total Completed Inspections - 16
Date Description Inspector Results Comments
08/15/2006 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
- CONDENSATE DRAINS TO BE 3/4" ENTIRE LENGTH.
- PROVIDE A TRAP ON FAN COIL DRAINS 2ND FLR & 1ST FLR
- PROVIDE A SHEET METAL VENT CONNECTOR WITH MIN. 3 SCREWS IN EACH JOINT 1ST FLOOR FURNACE.
- MUST USE DOUBLE WALL OUTSIDE.
- OPEN FAN COILS & REPAIR ANY WATER LEAKS.
- REPAIR INSULATION ON CONDENSOR PIPING & SUPPORT REFER LINES.
- PROVIDE A DRAIN ON COOLING TOWER TO AN APPROVED LOCATION.
08/15/2006 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
1. FILL UNUSED OPENINGS IN PANELS AND LABEL BREAKERS
2. MISSING OUTLET COVER
3. PROTECT BULB IN CLOSET
4. CORD NOT FOR PERMANENT WIRING
5. SUPPORT OUTLET IN CEILING GRID
6. USE APPROVED HANDLE TIE
7. MAINTAIN WORKING CLEARANCES IN FRONT OF PANELS
36" X 30"
8. FILL UNUSED OPENINGS IN JUNCTION BOXES
9. USE APPROVED FITTINGS
10. LABEL DISCONNECTS
11. USE APPROVED BOX COVERS
12. SUPPORT VDV CABLEING.
08/15/2006 OUTDOOR LIGHTING FINAL RHOLLAND Approved IVRS - Inspection :*
08/15/2006 ELECTRIC - OUTDOOR LIGHTING RHOLLAND Approved IVRS - Inspection :*
08/15/2006 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection :*
08/15/2006 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
08/16/2006 PLUMBING - FINAL BBENEDON Approved IVRS - Inspection :
See detailed listing on site.| 999*
- URINALS REQUIRE VACUUM BREAKERS AND A RIGDID PIPE CONNECTION.
- HOSE BIB REQUIRES A VAC BREAKERS
- ALL FIXTURES REQUIRE CAULKING AT CONNECTION TO FLOOR OR WALL.
- TOILETS REQUIRED TO HAVE OPEN FRONT SEATS.
- A SINK HAS BEEN ADDED WITHOUT INSPECTION, THIS MUST BE REMOVED OR PERMITTED.
- THE CONNECTION TO THE EXISTING PLUMBING SHALL BE EXPOSED FOR INSPECTION.
- WATER HEATER T&P NOT TERMINATED, PIPING NOT SUPPORTED. VALVE NOT FULL PORT.
01/31/2007 BUILDING - FINAL GDABBS Approved IVRS - Inspection :*
02/01/2007 MECHANICAL - ABOVE CEILING JMILITEL Approved
02/01/2007 PLUMBING - INTERMEDIATE BBENEDON Approved
02/01/2007 NPPO - FINAL ACONNOR Approved N/A
02/01/2007 LANDSCAPE - FINAL ACONNOR Approved N/A
02/01/2007 RIGHT OF WAY - FINAL PWHIDDON Approved PER EMAIL
02/01/2007 FIRE - FINAL LTHOMAS Approved
04/27/2007 ENGINEERING - FINAL JBRUCKME Approved
06/07/2007 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*

Documents

File Name Document Type  
C OF O_06-12-2007.TIF CERT OF OCC VIEW
None DOCUMENTS VIEW
REV#1.TIF CONSTRPLANS VIEW
ORIGINAL.TIF CONSTRPLANS VIEW
4256-01-0002-01-0002.TIF CONSTRPLANS VIEW
4256-01-0002-01-0003.TIF CONSTRPLANS VIEW
000_0609.JPG SIGNS VIEW