Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/04/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS 1, 7, 10, 12 |
|
| 08/15/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FILL UNUSED OPENINGS IN PANELS AND LABEL BREAKERS 2. MISSING OUTLET COVER 3. PROTECT BULB IN CLOSET 4. CORD NOT FOR PERMANENT WIRING 5. SUPPORT OUTLET IN CEILING GRID 6. USE APPROVED HANDLE TIE 7. MAINTAIN WORKING CLEARANCES IN FRONT OF PANELS 36" X 30" 8. FILL UNUSED OPENINGS IN JUNCTION BOXES 9. USE APPROVED FITTINGS 10. LABEL DISCONNECTS 11. USE APPROVED BOX COVERS 12. SUPPORT VDV CABLEING. |