Permit: T06CM04256

Parcel: 13316025E

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/30/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
01/19/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
DOUBLE WALL PIPE REQUIRED FROM POINT OF PENETRATION THRU WALL TO 2' ABOVE ROOF. SINGLE WALL VENT PIPE NOT ALLOWED OUTDOORS.
01/04/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. STILL NEED SCREWS 1ST FLOOR FURNACE VENT. NO TAPE!
2. VENT ON CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP.
3. PROVIDE DRAIN FOR COOLING TOWER
4. PROVIDE A DOUBLE WALL VENT FOR FIRST FLOOR.
5. FURNACES SECURED TO WALL OUTSIDE & TERMINATE 2' ABOVE ROOF.
08/15/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- CONDENSATE DRAINS TO BE 3/4" ENTIRE LENGTH.
- PROVIDE A TRAP ON FAN COIL DRAINS 2ND FLR & 1ST FLR
- PROVIDE A SHEET METAL VENT CONNECTOR WITH MIN. 3 SCREWS IN EACH JOINT 1ST FLOOR FURNACE.
- MUST USE DOUBLE WALL OUTSIDE.
- OPEN FAN COILS & REPAIR ANY WATER LEAKS.
- REPAIR INSULATION ON CONDENSOR PIPING & SUPPORT REFER LINES.
- PROVIDE A DRAIN ON COOLING TOWER TO AN APPROVED LOCATION.