Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL |
|
| 01/19/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DOUBLE WALL PIPE REQUIRED FROM POINT OF PENETRATION THRU WALL TO 2' ABOVE ROOF. SINGLE WALL VENT PIPE NOT ALLOWED OUTDOORS. |
|
| 01/04/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. STILL NEED SCREWS 1ST FLOOR FURNACE VENT. NO TAPE! 2. VENT ON CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP. 3. PROVIDE DRAIN FOR COOLING TOWER 4. PROVIDE A DOUBLE WALL VENT FOR FIRST FLOOR. 5. FURNACES SECURED TO WALL OUTSIDE & TERMINATE 2' ABOVE ROOF. |
|
| 08/15/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - CONDENSATE DRAINS TO BE 3/4" ENTIRE LENGTH. - PROVIDE A TRAP ON FAN COIL DRAINS 2ND FLR & 1ST FLR - PROVIDE A SHEET METAL VENT CONNECTOR WITH MIN. 3 SCREWS IN EACH JOINT 1ST FLOOR FURNACE. - MUST USE DOUBLE WALL OUTSIDE. - OPEN FAN COILS & REPAIR ANY WATER LEAKS. - REPAIR INSULATION ON CONDENSOR PIPING & SUPPORT REFER LINES. - PROVIDE A DRAIN ON COOLING TOWER TO AN APPROVED LOCATION. |