Permit: T06CM01753
Permit Details
Status:
Final
Type:
COMMERCIAL NEW
Address:
6984 E CENTURY PARK DR
Address NEW:
6984 E CENTURY PARK DR
Apply Date:
03/28/2006
Applicant:
LEVIN AND SONS L L C
Description:
NEW: WAREHOUSE SHELL
Contractors:
- LEVIN AND SONS L L C
Permit Reviews
Permit Number - T06CM01753
Permit Status: Final
Permit Description: NEW: WAREHOUSE SHELL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/28/2006 | PLANS OK TO SUBMIT - 3RD PARTY | 03/28/2006 | COMPLETED |
| 03/28/2006 | 3RD PARTY REVIEW-COMMERCIAL | 04/13/2006 | COMPLETED |
| 04/13/2006 | POST 3RD PARTY REVIEW | 05/16/2006 | COMPLETED |
| 07/12/2007 | REVISION - - 1ST | 07/12/2007 | COMPLETED |
| 07/27/2006 | RESUBMITTAL | 11/21/2006 | COMPLETED |
| 07/27/2006 | SITE | 07/28/2006 | COMPLETED |
| 07/28/2006 | OTHER | 07/28/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM01753
Permit Status: Final
Permit Description: NEW: WAREHOUSE SHELL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/28/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T06CM01753
Permit Description: NEW: WAREHOUSE SHELL
Total Completed Inspections - 40
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2006 | BUILDING PRE-SLAB | GDABBS | Approved | IVRS - Inspection :* BLDG. CLOSURE POUR AT COLUMN LINE #1 |
| 10/05/2006 | ELECTRIC - UNDERGROUND | RSUBA | Approved | IVRS - Inspection :* - OK 5 2 1/2" FROM CENTER LINE TO COL'S TO SERVICE SECTION. - OK 4" (1) AT FUTURE EQUIPMENT PAD - OK 3 - 4" SERVICE FEEDERS - OK ALL CONDUITS UNDER SLAB @ WAREHOUSE SEE PLANS AS SIGNED OFF R. SUBA |
| 10/18/2006 | EXCAVATION/LAYOUT REBAR & ZON | GDABBS | Approved | IVRS - Inspection :* LOADING DOCK ON WEST SIDE FOOTING -- OK TO POUR |
| 11/09/2006 | REINFORCED MASONRY PRE-GROUT | IVR USER | Approved | IVRS - RI canceled |
| 11/15/2006 | PLUMBING - YARD WTR LINE/TEST | BBENEDON | Approved | IVRS - Inspection :* CORRECT DRIP AT UNION WIPE SOLDIER JOINTS |
| 11/16/2006 | FRAMING | GDABBS | Approved | IVRS - Inspection :* ROD BRACES & TUBE BRACES NOT COMPLETE OK TO CONTINUE |
| 11/20/2006 | PLUMBING - ROUGH, SOIL | RLEDONNE | Approved | IVRS - Inspection :* |
| 03/05/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | TMPP CLEARED PER R. HOLLANDER |
| 04/05/2007 | ELECTRIC - FINAL | RJIROUDE | Approved | IVRS - Inspection :* |
| 04/05/2007 | ELECTRIC - INTERMEDIATE | RJIROUDE | Approved | IVRS - Inspection :* |
| 04/05/2007 | ELECTRIC - TEMPORARY SERVICE | RJIROUDE | Approved | IVRS - Inspection :* |
| 04/16/2007 | PLUMBING - INTERMEDIATE | RRICH | Approved | CALL IN ALL PLUMBING INSPECTIONS THAT DO NOT HAVE APPROVAL & PROVIDE INSPECTION HISTORY FOR PLUMBING. 1. SUPPORT VENT PIPING THRU ROOF AT CORRECT INTERVALS ON VERTICAL AND PAINT EXTERIOR VENT PIPING. 2. PROVIDE PERM CAP AT FUTURE URINAL DRAIN STUB. 3. EXPOSE CLEAN OUT FOR UTILITY SINK & PROVIDE CORRECT COVER. 4. SHALL HAVE ONLY (1) SUP JOINT CONNECTION ON DOWNSTREAM SIDE OF P-TRAP AT KITCHEN SINKS. 5. EXPOSE CLEAN OUT FOR DRINKING FOUNTAINS. 6. WATER HEATER T&P DRAIN PENETRATION THRU BUILDING TO BE SEALED. 7. FLOOR SINKS TO BE ACCESSIBLE 8. ICE MAKER TO BE INSTALLED WITH CORRECT BACKFLOW PROTECTION AND CERTIFICATION IF REQUIRED, AND CORRECT DRAIN CONNECTIONS. 9. EXPOSE EXTERIOR SEWER CLEANOUTS & PROVIDE CORRECT TERMINATIONS. |
| 04/19/2007 | ELECTRIC - PROGRESS | RJIROUDE | Approved | |
| 04/19/2007 | ELECTRIC - OUTDOOR LIGHTING | RJIROUDE | Approved | |
| 04/19/2007 | OUTDOOR LIGHTING FINAL | RJIROUDE | Approved | |
| 04/19/2007 | ELECTRIC - CABLE DROP | RJIROUDE | Approved | |
| 04/19/2007 | ELECTRIC - UFER | RJIROUDE | Approved | |
| 04/23/2007 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* |
| 04/23/2007 | MECHANICAL - PROGRESS | JMILITEL | Approved | IVRS - Inspection :* |
| 04/23/2007 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* |
| 04/23/2007 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* T.I PLAN DELETED RESTROOM ON THIS PLAN |
| 04/23/2007 | SITE - SEWER | RRICH | Approved | IVRS - Inspection :* APPROVED RDLD ON PERMIT #T06CM04481 |
| 04/23/2007 | SEPTIC - SYSTEM | RRICH | Approved | IVRS - Inspection :* PIMA COUNTY APPROVED |
| 04/23/2007 | PLUMBING - PROGRESS | RRICH | Approved | IVRS - Inspection :* |
| 04/23/2007 | PLUMBING - PRE SLAB | RRICH | Approved | IVRS - Inspection :* |
| 04/23/2007 | FIRE - HYDRANTS | LTHOMAS | Approved | |
| 04/23/2007 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 04/23/2007 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
| 04/23/2007 | RIGHT OF WAY - FINAL | SDAMRON | Approved | PER EMAIL |
| 04/24/2007 | BUILDING - FINAL | GDABBS | Approved | IVRS - Inspection :* |
| 04/24/2007 | SHEET ROCK NAILING | GDABBS | Approved | IVRS - Inspection :* |
| 04/24/2007 | ROOF NAILING | GDABBS | Approved | IVRS - Inspection :* |
| 04/24/2007 | EXT METAL CLIPS/EXT SHEATHING | GDABBS | Approved | IVRS - Inspection :* |
| 04/24/2007 | FIRE - FINAL | LTHOMAS | Approved | |
| 04/25/2007 | BUILDING - PROGRESS | GDABBS | Approved | |
| 05/01/2007 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
| 06/06/2007 | NPPO - FINAL | ACONNOR | Approved | |
| 06/06/2007 | LANDSCAPE - FINAL | ACONNOR | Approved | |
| 07/13/2007 | PERMIT FINALED | NKALAHAR | Approved | |
| 07/13/2007 | ENGINEERING - FINAL | NKALAHAR | Approved | *RIP RAP OUTFALLS MISSING AT BASIN OUTLET AND AT END OF CONCRETE SWALE (NW CORNER) *MISSING CONCRETE SWALE FROM SE CORNER OF BUILDING TO EAST *NO CONCRETE SWALE THROUGH GRAVLE AREA ON EAST SIDE OF BUILDING *RIP RAP BANK STABILIZATION NOT INSTALLED NE SIDE OF SITE *TRASH ENCLOSURE AREA NOT BUILT *INLET SWALE NOT BUILT INTO BASIN FROM BUILDING CP-REMOVE ALL STORMWATER CONTROLS *SEE 7/9 ENTRY T06BU01077 AND T06BU01610 |