Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2007 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 03/16/2007 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1. NEED 90 AMP BREAKER FOR TRANSFORMER FEED 2. INSTALL BUSHINGS ON PVC CONDUITS WITH CONDUCTORS LARGER THAN #4 3. PROVIDE GFI PERFORMANCE TEST SHEET 4. OK PANEL B, PANEL R, PACKAGE LINE, 20 TON & 35 TON CRSHR. 5. GUTTER FILL OK BOTH GUTTERS |
|
| 03/13/2007 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* OK 30 CONDUCTORS OR LESS EACH GUTTER VERIFY 20% FILL ON ANY CROSS-SECTION |
|
| 03/09/2007 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1. PLEASE HAVE ENGINEER REVISE CHANGE FOR GUTTER FEED TO COMPLY WITH NEC FOR FILL & DERATING SUBMIT TO PLAN CHECK C.O.T FOR APPROVAL |
|
| 03/02/2007 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* | |
| 02/26/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* ALSO SEE 310.15 PART C SEE NOTES PREVIOUS INSPECTIONS |
|
| 02/22/2007 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* 1. COMPLETE PANEL TERMINATIONS 2. PERFORM GFI MAIN BREAKER TESTS & PROVIDE COPIES OF APPROVED TESTS TO INSPECTOR. 3. BOND WATER PIPING 4. VERIFY DISTRIBUTION GUTTER INSIDE BLD. NOT OVERFILL PER 366 NEC - MAY BE NECESSARY TO DERATE PER 310.15B ENGINEER OF RECORD TO CALCULATE FILL & VERIFY IN COMPLIANCE WITH NEC. PROVIDE LETTER. 5. BOND POSTING FOR TEMP POWER FOR TEST REQUIRED. OVER 30 CURRENT CARRING CONDUCTORS NEED TO DERATE PER 310.15B |