Permit: T06CM01753

Parcel: 14108002H

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
04/05/2007 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
03/16/2007 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
1. NEED 90 AMP BREAKER FOR TRANSFORMER FEED
2. INSTALL BUSHINGS ON PVC CONDUITS WITH CONDUCTORS LARGER THAN #4
3. PROVIDE GFI PERFORMANCE TEST SHEET
4. OK PANEL B, PANEL R, PACKAGE LINE, 20 TON & 35 TON CRSHR.
5. GUTTER FILL OK
BOTH GUTTERS
03/13/2007 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
OK 30 CONDUCTORS OR LESS EACH GUTTER
VERIFY 20% FILL ON ANY CROSS-SECTION
03/09/2007 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
1. PLEASE HAVE ENGINEER REVISE CHANGE FOR GUTTER FEED TO COMPLY WITH NEC FOR FILL & DERATING SUBMIT TO PLAN CHECK C.O.T FOR APPROVAL
03/02/2007 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
02/26/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
ALSO SEE 310.15 PART C
SEE NOTES PREVIOUS INSPECTIONS
02/22/2007 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*
1. COMPLETE PANEL TERMINATIONS
2. PERFORM GFI MAIN BREAKER TESTS & PROVIDE COPIES OF APPROVED TESTS TO INSPECTOR.
3. BOND WATER PIPING
4. VERIFY DISTRIBUTION GUTTER INSIDE BLD. NOT OVERFILL PER 366 NEC - MAY BE NECESSARY TO DERATE PER 310.15B ENGINEER OF RECORD TO CALCULATE FILL & VERIFY IN COMPLIANCE WITH NEC. PROVIDE LETTER.
5. BOND POSTING FOR TEMP POWER FOR TEST REQUIRED.

OVER 30 CURRENT CARRING CONDUCTORS NEED TO DERATE PER 310.15B