Description:
TI: RETAIL R1- bldg, plumbing, mechanical & elect. revisons
Contractors:
  • HAUGEBAK CONSTRUCTION COMPANY ,

Permit Reviews

Permit Number - T06CM00539
Permit Status: Closed
Permit Description: TI: RETAIL R1- bldg, plumbing, mechanical & elect. revisons
Start Date Submittal Complete Date Status  
01/24/2006 PLANS OK TO SUBMIT - 3RD PARTY 02/02/2006 COMPLETED Review Details
02/02/2006 3RD PARTY REVIEW-COMMERCIAL TI 03/10/2006 COMPLETED Review Details
03/10/2006 POST 3RD PARTY REVIEW 04/12/2006 COMPLETED Review Details
08/06/2007 REVISION - - 1ST 09/11/2007 COMPLETED Review Details
09/11/2007 POST 3RD PARTY REVIEW 09/19/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM00539
Permit Status: Closed
Permit Description: TI: RETAIL R1- bldg, plumbing, mechanical & elect. revisons
Total Outstanding Activity Conditions - 1
Date Name
01/24/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T06CM00539
Permite Description: TI: RETAIL R1- bldg, plumbing, mechanical & elect. revisons
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
HEALTH DEPT - FINAL 724-7908 N/A Not Inspected
09/25/2007 SIGN - FINAL N/A Partial Approval IVRS - Inspection :$ MUST RENEW PERMIT FOR ELEC ON SIGN # T00EL02047 AND HAVE INSP BEFORE FINAL C/O CAN BE ISSUED; TEMP C/O OK

Completed Inspections

Permit Status: Closed
Permit Number: T06CM00539
Permit Description: TI: RETAIL R1- bldg, plumbing, mechanical & elect. revisons
Total Completed Inspections - 22
Date Description Inspector Results Comments
07/25/2006 PLUMBING - INTERMEDIATE BBENEDON Approved IVRS - Inspection :*
SPECIAL INSP. WATER LINE REPAIR
PD W/WESTERN UNION MONEY ORDER 08535660251

2 1/2 COPPER WATER LINE REPAIR IN PARKING LOT
OK TO COVER
08/01/2006 ELECTRIC - INTERMEDIATE RMAJUTA Approved RECEIVED CK FOR $108.00 FOR BEFORE HRS. INSP. FROM JIM BENNETT - HANGEBAK CONST. COMPANY

1. PARTIAL OK EMT FOR CART CHARGING AREA
2. EMT 1 1/4" FEED DOWN WALL TO CHICKEN ROTISSIERE ALSO 1/2" INTERIOR HOOD SWITCH.
3. OK 1 1/4" EMT RUN & ASSORTED 1/2" CONDUITS ON RUN IN GENERAL SALES AREA NORTH WALL INCLUDING 12"X12" J-BOX

FROZEN FOOD CASES
1. OK 2 - 1" EMT RUNS FROM PNL PTL1 TO FREEZER SECTION & INCLUDING FREEZERS & TERMINATIONS.
08/09/2006 PLUMBING - ROUGH, SOIL RLEDONNE Approved IVRS - Inspection :*
MONEY ORDER #08-532660704
FLOOR SINK IN BAKERY/DELI PAN WASHER OK
08/11/2006 MECHANICAL - HOOD SYSTEMS JMILITEL Approved IVRS - Inspection :*
CHECKED WELDED GREASE DUCT FRONT DELI HOOD
OK TO FIRE WRAP
08/15/2006 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
FIRE WRAP OK ON FRONT DELI HOOD
08/15/2006 ENGINEERING - FINAL NKALAHAR Approved SLURRY WASHED OUT AT SW CORNER OF BUILDING

ALL POLLUTANTS ie. STUCCO, PAINT, DRYWALL, ETC. TO BE WASHED OUT IN A CONTAINED AREA AND THEN PUT IN DUMPSTER (HAULED AWAY)

HAUGEBAK CONST CO.
TALKED TO JOE ON THE PHONE/JIM SITE SUPER
01/30/2007 FIRE SPKLR - FINAL LLAKEY Approved
01/30/2007 FIRE - KITCHEN EXH HOOD FINAL LLAKEY Approved
01/31/2007 FIRE - FINAL LLAKEY Approved
07/17/2007 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
PROVIDE APPROVED PLANS
SEAL JOINTS ON EXHAUST DUCT
PROVIDE ACCESS TO ROOF
07/17/2007 BUILDING - FINAL GDABBS Approved IVRS - Inspection :*
NEED APPROVED PLANS ON SITE
07/17/2007 ELECTRIC - ABOVE CEILING RJIROUDE Approved IVRS - Inspection :*
09/25/2007 ELECTRIC - FINAL RJIROUDE Approved IVRS - Inspection :
See detailed listing on site.| 999*
1. MC CABLE RUN ON TOP OF CEILING GRID IN PRODUCE TO DELI NEEDS TO BE SUPPORTED PROPERLY
2. STRAP MC CABLE WITHIN 12" OF JUNCTION BOXES ON FEEDS TO TRACK LIGHTS
3. INSTALL EXTENSIONS ON RECEPTACLES INSTALLED IN WOOD PANELS
4. ENSURE RECEPTACLES SECURED TIGHTLY TO WALL SURFACE
5. RECALL WHEN COMPLETE & FOR REST AT FINAL
09/25/2007 PLUMBING - FINAL RRICH Approved IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ALL WORK SHOWN ON APPROVED PLAN, HAVE INSPECTIONS ON ALL NEW WORK & DEMO WORK, INSTALL PER APPROVED PLAN. SHOW PROOF OF CORRECT CAPS AT DELI FLOOR SINKS, PRODUCE DRY RACKS AND MEAT PREP FLOOR SINKS
09/25/2007 NPPO - FINAL ACONNOR Approved
09/25/2007 LANDSCAPE - FINAL ACONNOR Approved
04/03/2008 PLUMBING - ABOVE CEILING RRICH Approved IVRS - Inspection :*
04/04/2008 MECHANICAL - HOODS JMILITEL Approved IVRS - Inspection :*
04/04/2008 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
04/07/2008 RIGHT OF WAY - FINAL PWHIDDON Approved PER EMAIL
04/11/2008 BUILDING ABOVE CEILING GDABBS Approved
04/11/2008 BUILDING PRE-SLAB GDABBS Approved

Documents

File Name Document Type  
T06CM00539-R_001.TIF CONSTRPLANS VIEW
T06CM00539-R_002.TIF CONSTRPLANS VIEW
T06CM00539-R_003.TIF CONSTRPLANS VIEW
T06CM00539-R_004.TIF CONSTRPLANS VIEW
T06CM00539-R_005.TIF CONSTRPLANS VIEW
T06CM00539-R_006.TIF CONSTRPLANS VIEW
T06CM00539-R_007.TIF CONSTRPLANS VIEW
T06CM00539-R_008.TIF CONSTRPLANS VIEW
T06CM00539-R_009.TIF CONSTRPLANS VIEW
T06CM00539-R_010.TIF CONSTRPLANS VIEW
T06CM00539-R_011.TIF CONSTRPLANS VIEW
T06CM00539-R_012.TIF CONSTRPLANS VIEW
T06CM00539-R_013.TIF CONSTRPLANS VIEW
T06CM00539-R_014.TIF CONSTRPLANS VIEW
T06CM00539-R_015.TIF CONSTRPLANS VIEW
T06CM00539-R_016.TIF CONSTRPLANS VIEW
T06CM00539-R_017.TIF CONSTRPLANS VIEW
T06CM00539-R_018.TIF CONSTRPLANS VIEW
T06CM00539-R_019.TIF CONSTRPLANS VIEW
T06CM00539-R_020.TIF CONSTRPLANS VIEW
T06CM00539-R_021.TIF CONSTRPLANS VIEW
T06CM00539-R_022.TIF CONSTRPLANS VIEW
T06CM00539-R_023.TIF CONSTRPLANS VIEW
T06CM00539-R_024.TIF CONSTRPLANS VIEW
T06CM00539-R_025.TIF CONSTRPLANS VIEW
T06CM00539-R_026.TIF CONSTRPLANS VIEW
T06CM00539-R_027.TIF CONSTRPLANS VIEW
T06CM00539-R_028.TIF CONSTRPLANS VIEW
T06CM00539-R_029.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW