Permit: T06CM00539

Parcel: 13405119H


Addresses:

9401 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/01/2006 ELECTRIC - INTERMEDIATE Approved RECEIVED CK FOR $108.00 FOR BEFORE HRS. INSP. FROM JIM BENNETT - HANGEBAK CONST. COMPANY

1. PARTIAL OK EMT FOR CART CHARGING AREA
2. EMT 1 1/4" FEED DOWN WALL TO CHICKEN ROTISSIERE ALSO 1/2" INTERIOR HOOD SWITCH.
3. OK 1 1/4" EMT RUN & ASSORTED 1/2" CONDUITS ON RUN IN GENERAL SALES AREA NORTH WALL INCLUDING 12"X12" J-BOX

FROZEN FOOD CASES
1. OK 2 - 1" EMT RUNS FROM PNL PTL1 TO FREEZER SECTION & INCLUDING FREEZERS & TERMINATIONS.
07/28/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PANEL PTL-1
ELEC. CIRCUITS & PANEL FEEDERS
NOTE: REFRIGERATION WIRING IS NOT INSTALLED AT PRESENT (THIS NEEDS TO BE LOOKED AT PRIOR TO ENERGIZING)
TO SCHEDULE AFTER HRS. INSPECTION -
SUPERVISOR RAY MAJUTA 909-5184
INSP. BOB SUBA 954-0161
07/27/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BUSHINGS ON ALL CONDUITS WITH #4 OR LARGER CONDUCTORS AT PANEL @ BACK.
2. CONTRACTOR NEEDS TO BE AVAILABLE FOR INSPECTION LEAVE MESSAGE FOR ME AT MESSAGE OPTION WHEN YOU SCHEDULE YOUR INSPECTION NEXT TIME.
MY PERSONAL CELL # IS 954-0161