Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM00539
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2006 | ELECTRIC - INTERMEDIATE | Approved | RECEIVED CK FOR $108.00 FOR BEFORE HRS. INSP. FROM JIM BENNETT - HANGEBAK CONST. COMPANY 1. PARTIAL OK EMT FOR CART CHARGING AREA 2. EMT 1 1/4" FEED DOWN WALL TO CHICKEN ROTISSIERE ALSO 1/2" INTERIOR HOOD SWITCH. 3. OK 1 1/4" EMT RUN & ASSORTED 1/2" CONDUITS ON RUN IN GENERAL SALES AREA NORTH WALL INCLUDING 12"X12" J-BOX FROZEN FOOD CASES 1. OK 2 - 1" EMT RUNS FROM PNL PTL1 TO FREEZER SECTION & INCLUDING FREEZERS & TERMINATIONS. |
|
| 07/28/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PANEL PTL-1 ELEC. CIRCUITS & PANEL FEEDERS NOTE: REFRIGERATION WIRING IS NOT INSTALLED AT PRESENT (THIS NEEDS TO BE LOOKED AT PRIOR TO ENERGIZING) TO SCHEDULE AFTER HRS. INSPECTION - SUPERVISOR RAY MAJUTA 909-5184 INSP. BOB SUBA 954-0161 |
|
| 07/27/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BUSHINGS ON ALL CONDUITS WITH #4 OR LARGER CONDUCTORS AT PANEL @ BACK. 2. CONTRACTOR NEEDS TO BE AVAILABLE FOR INSPECTION LEAVE MESSAGE FOR ME AT MESSAGE OPTION WHEN YOU SCHEDULE YOUR INSPECTION NEXT TIME. MY PERSONAL CELL # IS 954-0161 |