Permit: T06CM00539

Parcel: 13405119H


Addresses:

9401 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM00539

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/25/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
RECALL WHEN READY
09/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MC CABLE RUN ON TOP OF CEILING GRID IN PRODUCE TO DELI NEEDS TO BE SUPPORTED PROPERLY
2. STRAP MC CABLE WITHIN 12" OF JUNCTION BOXES ON FEEDS TO TRACK LIGHTS
3. INSTALL EXTENSIONS ON RECEPTACLES INSTALLED IN WOOD PANELS
4. ENSURE RECEPTACLES SECURED TIGHTLY TO WALL SURFACE
5. RECALL WHEN COMPLETE & FOR REST AT FINAL
07/17/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEED REVISED & APPROVED SET OF DRAWINGS FOR WORK THAT WAS DONE
2. WHEN CALLING FOR FINALS NEED TO INSPECT STORE IN SECTIONS. ALSO, NO CEILING INSPECTIONS WERE DONE
NEED TO HAVE LADDER OR LIFT TO INSPECT CEILINGS.
3. RECALL WHEN READY
03/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEED REVISED SET OF DRAWINGS THAT SHOWS EXACTLY WHAT WORK HAS BEEN DONE & WHAT WAS ELIMINATED.
01/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY OFFICE