Permit: T05CM05444
Permit Details
Apply Date:
10/26/2005
Applicant:
CHAVEZ LARRY
Description:
NEW BLDG:OFFICE,CABINET SHOP,WAREHOUSE
Contractors:
- WOODCRAFTERS CABINET COMPANY INC
Permit Reviews
Permit Number - T05CM05444
Permit Status: C of o
Permit Description: NEW BLDG:OFFICE,CABINET SHOP,WAREHOUSE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/02/2007 | REVISION - SITE | 01/08/2007 | COMPLETED |
| 01/16/2006 | 3RD PARTY REVIEW-REVISION/OTHER | 01/20/2006 | COMPLETED |
| 04/24/2006 | 3RD PARTY REVIEW-REVISION/OTHER | 05/08/2006 | COMPLETED |
| 10/26/2005 | PLANS OK TO SUBMIT - COMM | 10/26/2005 | COMPLETED |
| 10/26/2005 | PLANS OK TO SUBMIT - SITE | 10/26/2005 | COMPLETED |
| 10/26/2005 | SITE | 11/22/2005 | COMPLETED |
| 10/27/2005 | 3RD PARTY REVIEW-COMMERCIAL | 12/14/2005 | COMPLETED |
| 11/29/2005 | RESUBMITTAL - SITE ALL | 12/08/2005 | COMPLETED |
| 12/08/2005 | RESUBMITTAL - SITE | 12/12/2005 | COMPLETED |
| 12/12/2005 | RESUBMITTAL - SITE | 12/21/2005 | COMPLETED |
| 12/14/2005 | POST 3RD PARTY REVIEW | 12/21/2005 | COMPLETED |
| 12/15/2006 | REVISION - SITE | 01/02/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM05444
Permit Status: C of o
Permit Description: NEW BLDG:OFFICE,CABINET SHOP,WAREHOUSE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/26/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T05CM05444
Permit Description: NEW BLDG:OFFICE,CABINET SHOP,WAREHOUSE
Total Completed Inspections - 39
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2006 | ELECTRIC - UFER | RMAJUTA | Approved | IVRS - Inspection : See detailed listing on site.| 999*11:30 AM CONCRETE ALREADY POURED |
| 03/07/2006 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :* 1. ARCHITECT APPROVES ABS DWV BLDG. DRAIN 2. ABS DWV UNDER SLAB OK TO COVER CONTRACTOR TO WRAP PIPE BEFORE POURING CONCRETE. 3. 3 SETS OF RWL ALONG WEST SIDE OF OK UNDER SLAB 4. WATER SERVICE STUBBED IN UNDER SLAB OK OK TO COVER |
| 03/22/2006 | BUILDING PRE-SLAB | AQUIROZ | Approved | IVRS - Inspection :* |
| 06/16/2006 | ROOF NAILING | JBURGE | Approved | IVRS - Inspection :* |
| 07/27/2006 | PLUMBING - ROOF DRAINS | BBENEDON | Approved | IVRS - Inspection :* |
| 08/07/2006 | MECHANICAL - INTERMEDIATE | CWILLIAM | Approved | IVRS - Inspection :* 1. PRIOR TO FINAL, HAVE OWNER SUPPLY LETTER APPROVING ZONE DAMPERS BEING DELETED FROM 2ND FLOOR. 2. FIRE DAMPERS ACCESS PANELS. WILL LOCATE ON WAREHOUSE SIDE, TOP OF SHT. MTL. DUCTS, TOP OF OFFICE. |
| 08/09/2006 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* |
| 08/15/2006 | PLUMBING - SEWER HCS CONNECT | BBENEDON | Approved | IVRS - Inspection :* |
| 08/23/2006 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
| 10/18/2006 | EXCAVATION/LAYOUT REBAR & ZON | AQUIROZ | Approved | IVRS - Inspection :* |
| 11/03/2006 | ELECTRIC - TEMP POWER FOR TEST | CCLEMENS | Approved | IVRS - Inspection :* 1) NOTE: BOND SECONDARY RACEWAYS IN SERVICE |
| 11/06/2006 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED PER C. CLEMENS |
| 11/09/2006 | PLUMBING - INTERMEDIATE | BBENEDON | Approved | IVRS - Inspection :* GAS PIPING NOT PER PLAN 1. 2 1/2" REQUIRED TO BRANCH CONNECTION 2. FUTURE PIPE BRANCH NOT SHOWN 3. USE 15 PSI GAUGE WITH 1/10 PSI INCREMENTATION |
| 11/09/2006 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection :* |
| 11/09/2006 | REINFORCED MASONRY PRE-GROUT | AQUIROZ | Approved | IVRS - Inspection :* |
| 11/15/2006 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* |
| 11/17/2006 | PLUMBING - FINAL | RMYERS | Approved | PLUMBING FINAL OK OK FOR C OF O S.T.O.I 1. SUPPLY INSPECTION HISTORY FOR SEWER/HCS INSPECTION OK |
| 11/17/2006 | PLUMBING - GAS PRESS TEST FNL | RMYERS | Approved | |
| 11/17/2006 | PLUMBING - ABOVE CEILING | RMYERS | Approved | |
| 11/17/2006 | MECHANICAL - FINAL | CWILLIAM | Approved | IVRS - Inspection :* |
| 11/29/2006 | SIGN - FINAL | JYBARRA | Approved | |
| 11/30/2006 | RIGHT OF WAY - FINAL | MOTERO | Approved | PER EMAIL NOTE: 1. Header curb install without survey done. 2. In case of future right-of-way improvements Sierra Trust Holdings LLC will reimburse the City of Tucson all costs and labor for any work found to be additional for improvements of above stated curb per agreement with Larry Chavez. |
| 11/30/2006 | NPPO - FINAL | ACONNOR | Approved | |
| 11/30/2006 | LANDSCAPE - FINAL | ACONNOR | Approved | |
| 12/04/2006 | U VALUE FOR WINDOW | JBURGE | Approved | IVRS - Inspection :* TEMPERED GLASS & FIRE SHELTERS |
| 12/04/2006 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
| 12/05/2006 | ENGINEERING - FINAL | MRUSSO | Approved | 1) COMPLETE SITE WORK IN RIGHT OF WAY. 2) INSTALL HC SIGNS IN ACCORDANCE WITH PLANS. 3) I WILL CONVEY THE ARCHETECH STAMPED LETTER DESCRIBING CHANGES MADE TO THE APPROVED PLANS TO THE CITY OF TUCSON REVIEWER FOR APPROVAL. 4) CALL IN FOR FINAL GRADING INSPECTION (#9190) FOR PERMIT #T05BU02832. 5) THE CITY MAY REQUIRE AN AS-BUILT DRAWING CHANGES MADE. |
| 12/06/2006 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
| 12/12/2006 | ELECTRIC - INTERMEDIATE | CCLEMENS | Approved | IVRS - Inspection :* PANEL SCHEDULES ARE NOT PROPERLY IDENTIFIED - GO THROUGH ALL CKTS AND MAKE SURE THEY ARE MARKED AND GOING TO WHAT THEY SAY THEY ARE GOING TO -- NEC 408.4 |
| 12/12/2006 | FIRE - FINAL | LTHOMAS | Approved | |
| 12/12/2006 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 12/12/2006 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 12/12/2006 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 12/12/2006 | OUTDOOR LIGHTING FINAL | CCLEMENS | Approved | IVRS - Inspection :* |
| 12/12/2006 | ELECTRIC - OUTDOOR LIGHTING | CCLEMENS | Approved | IVRS - Inspection :* |
| 12/14/2006 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection :* |
| 12/14/2006 | STUCCO MESH | IVR USER | Approved | IVRS - AP canceled |
| 12/15/2006 | EXT METAL CLIPS/EXT SHEATHING | AQUIROZ | Approved | IVRS - Inspection :* |
| 01/08/2007 | BUILDING - FINAL | AQUIROZ | Approved |