Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* PANEL SCHEDULES ARE NOT PROPERLY IDENTIFIED - GO THROUGH ALL CKTS AND MAKE SURE THEY ARE MARKED AND GOING TO WHAT THEY SAY THEY ARE GOING TO -- NEC 408.4 |
|
| 12/04/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 11/09/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 10/25/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. INSPECTION FOR SERVICE NOT READY, MAIN FEEDERS NOR SUB-FEEDERS NOT PULLED IN. 2. NEED A PERFORMANCE BOND FOR TEMP POWER, NEED TO FINISH CONDUITS INTO TEP TRANSFORMER & PULL IN AND TERMINATE CONDUCTORS. |
|
| 08/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRICAL COVER FRONT OFFICE AREA & 2ND FLOOR. |
|
| 08/10/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT BOXES PER 314.23(B)(2) 2. PLEASE VERIFY USAGE OF M/C CABLE PLANS CALL FOR CONDUIT SYSTEM. 3. CONNECT RACEWAYS - JUNCTION BOXES TO BE ACCESSIBLE 4. VERIFY BOX FILL 5. SUPPORT M/C CABLE ON HORIZONTAL RUNS 6. PROTECT CONDUCTOR FROM SCREWS 314.43 7. SUPPORT CABLE FROM SUPPOT NOT EACH OTHER AND WITHIN 12" OF BOXES & CAS 8. SUPPORT VDV CABELING IN WALL 725.6 9. CONDUIT RUNS NOT TO BE MORE THAN 360 DEG. |
|
| 03/16/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER FLOOR RECEPT UNDERGROUND |
|
| 03/07/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FEED CONDUITS UNDER SLAB - SUBJECT TO ENGINEER 1. PLEASE ADD 02010 TO PERMIT 2. PLEASE VERIFY WITH A LETTER AUTHORIZING USE OF PVC UNDER SLAB. ALSO IS AREAS FALL UNDER 500.5 (C)(1) OR (2) OR 500.5 (D)(1) OR (2) |