Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* GAS PIPING NOT PER PLAN 1. 2 1/2" REQUIRED TO BRANCH CONNECTION 2. FUTURE PIPE BRANCH NOT SHOWN 3. USE 15 PSI GAUGE WITH 1/10 PSI INCREMENTATION |
|
| 09/26/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RECEIVED LETTER; OK TO USE PVC FOR YARD WATER PVC YARD WATER OK TO COVER, RECALL FOR INSPECTION AFTER INSTALLING RP AND METER. |
|
| 09/20/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PVC WITH 100 PSI AIR TEST IS A SAFETY HAZARD AND AN OSHA VIOLATION. HYDROSTATIC TEST W/WATER. PLAN SPECS COPPER, PLEASE PROVIDE A LETTER FROM GLHN ALLOWING PVC. |
|
| 08/07/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CONDENSATE CANNOT PIPE TO HAND SINK, PIPE TO MOP SINK OK TO COVER AFTER CORRECTING CONDENSATE ALSO DOCUMENTATION FOR USE OF ABS SHALL INCLUDE ENTIRE PROJECT EXCEPT N. WALL ROOF DRAINS WATER PIPING - ALL EXCEPT COOLERS OK TO COVER GAS PIPING W/68 PSI TEST ALL EXCEPT FOR ROOFTOP UNITS IN SHOP AREA. |
|
| 07/27/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - PLAN SPECIFIES CAST IRON -- PROVIDE DOCUMENTATION - DWV, WATER AND RD TEST IS OK - OK TO INSULATE - RECALL INSPECTION WHEN COMPLETED. - INSTALL SAFETY PLATES ON PIPES WITHIN 1 1/4" FROM ROUGH STUD - BRASS SCREWS REQUIRED ON CLOSET FLANGES NOT PLATED SCREWS - SECURE ICE MAKER BOX - WH DRAIN PAN DRAIN LINE NOT INSTALLED - SECURE DROP AT HB - INSTALL 4" END OF LINE CLEAN OUT IN WALL - CLOSET FLANGES 1ST FLOOR NOT INSTALLED. |
|
| 07/20/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. ADD SUPPORT FIX LEAKS ROOF DRAINS 2. INTERMEDIATES NOT DONE WITH WALLS |