Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
06/01/2005
Applicant:
CARHUFF, PHILIP ANDREW
Description:
INSTALL:A/C UNIT W/ELECTRIC
Architects:
  • CARHUFF, PHILIP ANDREW
Contractors:
  • ROCKING M CONSTRUCTION INC ,

Permit Reviews

Permit Number - T05CM02493
Permit Status: Expired
Permit Description: INSTALL:A/C UNIT W/ELECTRIC
Start Date Submittal Complete Date Status  
09/15/2005 OTHER 12/01/2005 COMPLETED Review Details
12/01/2005 OTHER 12/02/2005 COMPLETED Review Details
12/02/2005 OTHER 12/02/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM02493
Permit Status: Expired
Permit Description: INSTALL:A/C UNIT W/ELECTRIC
Total Outstanding Activity Conditions - 1
Date Name
06/01/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T05CM02493
Permite Description: INSTALL:A/C UNIT W/ELECTRIC
Total Outstanding Inspections - 6
Last Inspection Date Description Inspector Results Comments
FRAMING N/A Not Inspected
BUILDING - FINAL N/A Not Inspected
PLUMBING - FINAL N/A Not Inspected
02/15/2007 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO PLANS OR PERMIT ON SITE
2. CORRECTLY INSTALL HIGH LEG AS PER NEC PAST CT CAN AT PANEL.
3. IDENTIFY HIGH LEG CONDUCTORS AT ALL POINTS PER CODE
4. VERIFY DERATING OF CONDUCTORS PER
BOTH 310.15 & 310.16
5. PLEASE DRIVE GROUND RODS FLUSH
6. NEED ACCESS TO ROOF
7. ONLY ONE CONDUCTOR PER LUG - GROUNDS
8. PLEASE MOVE GROUNDING ELECTRODE CONDUCTOR TO PANEL SO AS NOT TO BE IN LOCKED CABINET FOR ACCESS.
03/08/2007 ELECTRIC - INTERMEDIATE N/A Partial Approval IVRS - Inspection :*
1) SUPPORT VDV CABELING
2) CLEANOUT BOTTOM OF PANEL C
3) FINISH WIRING IN PANEL C
03/30/2007 PLUMBING - GAS PRESSURE TEST N/A Not ready for Inspection IVRS - Inspection :*
REMOVE THREAD PROTECTOR AT RISER TO ROOF
RETEST SUPPORT BRANCH PIPING AT CONNECTION TO MAIN AND AT EQUIPMENT.

Completed Inspections

Permit Status: Expired
Permit Number: T05CM02493
Permit Description: INSTALL:A/C UNIT W/ELECTRIC
Total Completed Inspections - 5
Date Description Inspector Results Comments
12/18/2006 BUILDING ABOVE CEILING JBURGE Approved IVRS - Inspection :*
CORRECTIONS COMPLETED FROM INSPECTION OF 8/29/06
03/05/2007 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
03/05/2007 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
1. PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTORS -- WILL CHECK ON FINAL
2. PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING.
3. PROVIDE FUSES IN ELEC. DISCONNECTS.
4. OK FOR CEILING TILES.
03/09/2007 TEP CLEARANCE - AM JWEATHER Approved TMPP CLEARED PER R. JIROUDEK
11/27/2007 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
1) AIR BALANCE OK
2) CORRECTIONS HAVE BEEN MADE
3) OK FOR FINAL