Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO PLANS OR PERMIT ON SITE 2. CORRECTLY INSTALL HIGH LEG AS PER NEC PAST CT CAN AT PANEL. 3. IDENTIFY HIGH LEG CONDUCTORS AT ALL POINTS PER CODE 4. VERIFY DERATING OF CONDUCTORS PER BOTH 310.15 & 310.16 5. PLEASE DRIVE GROUND RODS FLUSH 6. NEED ACCESS TO ROOF 7. ONLY ONE CONDUCTOR PER LUG - GROUNDS 8. PLEASE MOVE GROUNDING ELECTRODE CONDUCTOR TO PANEL SO AS NOT TO BE IN LOCKED CABINET FOR ACCESS. |