Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM02493
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO PLANS OR PERMIT ON SITE 2. CORRECTLY INSTALL HIGH LEG AS PER NEC PAST CT CAN AT PANEL. 3. IDENTIFY HIGH LEG CONDUCTORS AT ALL POINTS PER CODE 4. VERIFY DERATING OF CONDUCTORS PER BOTH 310.15 & 310.16 5. PLEASE DRIVE GROUND RODS FLUSH 6. NEED ACCESS TO ROOF 7. ONLY ONE CONDUCTOR PER LUG - GROUNDS 8. PLEASE MOVE GROUNDING ELECTRODE CONDUCTOR TO PANEL SO AS NOT TO BE IN LOCKED CABINET FOR ACCESS. |