Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM02493
Parcel: 127121200

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM02493
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM02493 7/15/05

1. HVAC Equipment Schedule specifies 230V equipment. Electrical service is 208V without transformation. Please clarify.
2. AC Unit #3 is specified as 3-phase on HVAC Equipment Schedule. The unit is on a 2-pole CB. Coordinate with Mechanical and clarify.
3. Loads listed on new Panel A from existing Panel C do not correspond to the totals on Panel Schedule C. Furthermore, the totals on Phases A and B on Panel C appear to be 17175 VA and 15300 VA, respectively.
4. Existing equipment on 240V panel may not be suited for 208V.
5. Provide available fault current at Panel C.
6. Per NEC Table 250.66, 500 MCM Cu takes a 1/0 Grounding Electrode Conductor, not #2.
09/15/2005 GBONILL1 BUILDING-COMMERCIAL REVIEW Denied
09/15/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation for the restrooms per Section 403.3, IMC 2000.
2. Provide duct insulation per Section 803.2.8, IECC 2000.
09/15/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/01/2005 GBONILL1 OUT TO CUSTOMER Completed