Permit: T05CM02493

Parcel: 127121200


Addresses:

5601 E BROADWAY BL

Inspection Status: Approved

Inspection History: BUILDING ABOVE CEILING

Date Description Inspector Results Comments
12/18/2006 BUILDING ABOVE CEILING Approved IVRS - Inspection :*
CORRECTIONS COMPLETED FROM INSPECTION OF 8/29/06
08/29/2006 BUILDING ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. YOU NEED NEW ENGINEERING TO MODIFY PLAN SEE DETAILS 1 & 2 PP. 5-1 NEW ROOF SUPPORTS TO BE AGAINST (FLUSH) METAL ROOF. YOU HAVE CURRENTLY HELD THEM DOWN BECAUSE OF ROOF SHEATHING SCREWS.
2. TO ELIMINATE C-CLAMPS GET LETTER FROM ENGINEER ALLOWING H.S BOLTS
3. RFI WITH ENGINEERS STAMP IS ACCEPTABLE