Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Address:
2550 N 14TH AV
Address NEW:
2550 N 14TH AV
Apply Date:
03/18/2005
Applicant:
N/A
Description:
TI:OFFICE
Architects:
  • MCCARTHY, BRIAN PATRICK
Contractors:
  • COOLEY CORPORATION

Permit Reviews

Permit Number - T05CM01217
Permit Status: Final
Permit Description: TI:OFFICE
Start Date Submittal Complete Date Status  
03/18/2005 COMMERCIAL TI 03/29/2005 COMPLETED Review Details
03/29/2005 3RD PARTY REVIEW-COMMERCIAL TI 06/06/2005 COMPLETED Review Details
04/12/2006 3RD PARTY REVIEW-REVISION/OTHER 04/17/2006 COMPLETED Review Details
06/06/2005 POST 3RD PARTY REVIEW 06/13/2005 COMPLETED Review Details
09/13/2005 3RD PARTY REVIEW-REVISION/OTHER 04/12/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM01217
Permit Status: Final
Permit Description: TI:OFFICE
Total Outstanding Activity Conditions - 1
Date Name
03/18/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T05CM01217
Permit Description: TI:OFFICE
Total Completed Inspections - 20
Date Description Inspector Results Comments
07/29/2005 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
1) IT HAS BEEN SIX WEEKS. HOW LONG DOES IT TAKE TO GET AN ADDRESS CORRECTION ?
2) SEE NOTE #1 FROM 6/16/05
3) CLOSET FLANGE OK
08/10/2005 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
08/10/2005 FRAMING AQUIROZ Approved IVRS - Inspection :*
09/16/2005 PLUMBING - ABOVE CEILING RRICH Approved IVRS - Inspection :*
2ND FLOOR ABOVE CEILING OK
10/02/2005 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :*2ND FLOOR ????PARTIAL
10/06/2005 ELECTRIC - ABOVE CEILING RMAJUTA Approved PARTIAL CEILING-FOLD MECH CLIP ON FIXTURE OVER T-BAR
LETTER FROM ENG ON OMITING EM LIGHTS
10/10/2005 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
10/17/2005 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection :*
10/24/2005 ELECTRIC - INTERMEDIATE RMAJUTA Approved 1) BLDG 2550, ? COPPER UFER TO 2 GRD RODS ALSO 3-2 1/2" CONDUITS TO GENERATOR ROOM OK
2) 3-2 1/2" FROM GENERATOR TO SERVICE
10/24/2005 ELECTRIC - UFER RMAJUTA Approved IVRS - Inspection :*
10/31/2005 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*
11/14/2005 SIGN - FINAL RDEAR Approved IVRS - Inspection :*
11/21/2005 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection :*OK FOR TEMP C OF O 2ND STORY
#1 LABLE GENERATOR DISCONNECT AT BLDG ENTRY
# 2 RE IDENTIFY WHITE CONDUCTORS BEING USED AS HOT'S
# 3 GENERATORS TO BE INSTALLED FOR FINAL
11/28/2005 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :*
11/29/2005 FIRE SPKLR - FINAL LTHOMAS Approved
11/29/2005 FIRE - FINAL LTHOMAS Approved
12/06/2005 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL
12/07/2005 ENGINEERING - FINAL MRUSSO Approved TEMP C OF O FOR ENGINEERING APPROVED ONLY WITH THE CONDITION THAT THE CONTRACTOR/MANAGER:

1) PROVIDE A DETAILED PLAN DESCRIBING A SAFE PARKING AREA AND WALKWAY FOR EMPLOYEES TO ENTER AND EXIT THE REMODLED OFFICE, ALSO SEPARATE CONSTRUCTION ACTIVITY FROM ACCESS WAY.
2) PROVIDE BARRIERS AND/OR TEMPORARY FENCING THAT WILL SEPARATE CONSTRUCTION FROM THE OCCUPIED BLDG.
3) IMPLEMENT ACCESS PLAN DURING PARKING LOT CONSTRUCTION.
4) SEE ATTACHED PLAN.
5) CALL FOR REINSPECTION WHEN SITE WORK IS COMPLETED.
12/08/2005 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*OK TEMP C OF O
05/10/2006 PERMIT FINALED BFLORES Approved