Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* DICKIE LEE DON 2ND FLOOR |
|
| 02/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DICKIE LEE OR DERRICK CELL 405-5195 882-8142 405-5195 -- CALLED NA COULD NOT LEAVE MESSAGE 1. MAIN SW GEAR -- COLOR CODE CONDUCTORS, LIFT OF BUS BAR AND ISOLATE FROM ENCLOSURE. 2. OBTAIN CORRECT REVISIONS - PLAN TO BE REVISED TO SHOW EXACTLY WHAT IS ON JOB SITE - WIRE SIZES, CONDUIT SIZES WIRING DIAGRAM FRO TRANSFER SWITCHES. 3. REMOVE EXCESS WIRE IN GENERATOR TERMINAL 4. CONNECT ALL GROUND BUSHING TO ENCLOSURE WITH CORRECT SIZE WIRING. |
|
| 11/21/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*OK FOR TEMP C OF O 2ND STORY #1 LABLE GENERATOR DISCONNECT AT BLDG ENTRY # 2 RE IDENTIFY WHITE CONDUCTORS BEING USED AS HOT'S # 3 GENERATORS TO BE INSTALLED FOR FINAL |