Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/21/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*NEED TO ID UNITS W/NUMBERS WEST CARRIER UNIT 5 TON A) DATA PLATE NOT COMPLETED. STRAIGHT HEAT PUMP FUSES AT 30 AMPS MAX/ IF UNIT HAS AUXILIARY HEAT STRIPS DATA PLATE SHOULD BE MAKED ACCORDINGLY LEAVE UNIT PROPERLY FUSED, SWITCH HAS 60 AMP FUSES. CONDENSATE DRAINIS CURRENTLY TERMINATED INTO WASTE VENT, INCORRECT, NOT ACCEPTABLE. ALL OTHER ROOF TOP UNITS, DRAINING CONDENSATES DOWN ON TO SIDE WALK ON SOUTH SIDE OF BUILDING, INCORRECT, NOT ACCEPTABLE. SUGGESTION- COLLECT ALL CONDENSATE DRAINS AND RUN INTO MOP SINK IN RM. WITH ROOF ACCESS. |