Start Date Submittal Complete Date Status  
01/19/2005 3RD PARTY REVIEW-REVISION/OTHER 01/20/2005 COMPLETED Review Details
01/20/2005 POST 3RD PARTY REVIEW 01/20/2005 COMPLETED Review Details
03/07/2005 3RD PARTY REVIEW-REVISION/OTHER 03/09/2005 COMPLETED Review Details
04/07/2005 3RD PARTY REVIEW-REVISION/OTHER 04/11/2005 COMPLETED Review Details
04/11/2005 POST 3RD PARTY REVIEW 04/12/2005 COMPLETED Review Details
07/02/2004 PLANS OK TO SUBMIT - 3RD PARTY 07/02/2004 COMPLETED Review Details
07/02/2004 3RD PARTY REVIEW-COMMERCIAL 08/27/2004 COMPLETED Review Details
08/27/2004 POST 3RD PARTY REVIEW 09/29/2004 COMPLETED Review Details
09/29/2004 RESUBMITTAL 10/22/2004 COMPLETED Review Details
10/22/2004 3RD PARTY REVIEW-REVISION/OTHER 11/01/2004 COMPLETED Review Details
11/08/2004 3RD PARTY REVIEW-REVISION/OTHER 11/15/2004 COMPLETED Review Details
12/07/2004 POST 3RD PARTY REVIEW 12/08/2004 COMPLETED Review Details
12/07/2004 3RD PARTY REVIEW-REVISION/OTHER 12/13/2004 COMPLETED Review Details
12/28/2004 3RD PARTY REVIEW-REVISION/OTHER 12/30/2004 COMPLETED Review Details
12/28/2004 3RD PARTY REVIEW-REVISION/OTHER 01/11/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04CM03061
Permit Status: C of o
Permit Description: NEW:HIGH SCHOOL CLASSROOMS
Total Outstanding Activity Conditions - 1
Date Name
07/02/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T04CM03061
Permit Description: NEW:HIGH SCHOOL CLASSROOMS
Total Completed Inspections - 38
Date Description Inspector Results Comments
12/14/2004 ELECTRIC - UFER RSUBA Approved IVRS - Inspection :*/SCIENCE WING BUILDING 3 (#4 & #2) & 34DP 3/0 & #2 (TRANSF)
12/17/2004 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved IVRS - Inspection :*
12/23/2004 STEM WALL/RETAINING WALL LHANLY Approved IVRS - Inspection :*
1) ALONG EAST
12/29/2004 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
12/30/2004 PLUMBING - ROUGH, SOIL RRICH Approved IVRS - Inspection :WATER TEST WASTE AND VENT UNDERGROUND ONLY UNISEX 322 +323
AND P-8 IN WORK AREA 317 OK
12/30/2004 ELECTRIC - UNDERGROUND RSUBA Approved IVRS - Inspection :* 34 DP ( FEEDERS ) & 32 DP FEEDERS COMP & IDF FEEDERS
01/13/2005 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
01/26/2005 BUILDING PRE-SLAB LHANLY Approved IVRS - Inspection :*
02/24/2005 REINFORCED MASONRY PRE-GROUT LHANLY Approved IVRS - Inspection :*
03/03/2005 PLUMBING - SEWER HCS CONNECT RRICH Approved IVRS - Inspection :* APPROVED HCS CONNECTION INTO 6" SEWER SOUTH WEST OK. 1-4" HCS CONNECTION INTO 4" SEWER SOUTH EAST OK.
04/21/2005 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection :*
1) WATER TEST THRU ROOF WASTE AND VENT SCIENCE SECTION BLDG OK
2) BLDG 3 INTERMEDIATE-OK
3) 100 PSI TEST ALL OF BLDG 3 GAS PIPING OK
4) PARTIAL APPROVAL WAITING ON REVISED CITY APPROVED GAS ISOMETRIC
05/05/2005 PLUMBING - GAS PRESSURE TEST RRICH Approved IVRS - Inspection :* 100 PSI AIR TEST GAS SYSTEM FROM METER TO ALL FIXTURE STUBS WITH CAP OK
05/25/2005 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
1) CHECKED SUPPLY AND EXHAUST IN RESTROOMS-ROOMS 358 AND 357. APPROVED
2) OK FOR SHEET ROCK
06/10/2005 PLUMBING - ABOVE CEILING RRICH Approved IVRS - Inspection :*
07/08/2005 MECHANICAL - ABOVE CEILING RRICH Approved IVRS - Inspection :* DAMPERS INSTALLED IN ROOM 339 ELECTRIC STILL TO BE TERMINATED ROOM 365 OK
07/11/2005 PLUMBING - GAS PRESS TEST FNL RRICH Approved IVRS - Inspection :*(2) GAS CLEARANCE CARDS ISSUED SO METER MAY BE ORDERED. GAS IS NOT TO BE ACTIVATED UNTIL FIRE PROTECTION SYSTEM IS ACTIVATED.
07/13/2005 SHEET ROCK NAILING LHANLY Approved IVRS - Inspection :*
07/13/2005 FIRE - ALARM FINAL LTHOMAS Approved
07/15/2005 PLUMBING - YARD WTR LINE/TEST RRICH Approved IVRS - Inspection :*
07/18/2005 FIRE - FINAL LTHOMAS Approved
07/18/2005 FIRE - LANE SIGNS LTHOMAS Approved
07/18/2005 FIRE SPKLR - FINAL LTHOMAS Approved
07/18/2005 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
07/19/2005 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
1) OK FOR FINAL C OF O
07/19/2005 ROOF NAILING LHANLY Approved IVRS - Inspection :*
07/20/2005 BUILDING ABOVE CEILING LHANLY Approved IVRS - Inspection :*
07/20/2005 FRAMING LHANLY Approved IVRS - Inspection :*
07/20/2005 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
07/21/2005 ENGINEERING - FINAL JSALINE Approved TEMPORARY C OF O APPROVED.

FINAL C OF O TO BE ISSUED AFTER COMPLETION OF CONCRETE PER APPPROVED PLANS. COMPLETION OF ALL DRAINAGE REQUIREMENTS PER APPROVED PLANS. INSTALLATION OF ADDITIONAL SCUPPERS AS EXPLAINED TO CONTRACTOR, (LLOYDS CONSTRUCTION). COMPLETION OF ALL ROCK-RIP-RAP PER APPROVED PLANS.
08/03/2005 BUILDING - FINAL LHANLY Approved IVRS - Inspection :*
1) TCO MAY EXPAND TO INCLUDE LIBRARY AND ART ROOMS
08/03/2005 OUTDOOR LIGHTING FINAL RSUBA Approved IVRS - Inspection :*
08/03/2005 ELECTRIC - FINAL RSUBA Approved IVRS - Inspection :*
08/03/2005 ELECTRIC - ABOVE CEILING RSUBA Approved IVRS - Inspection :*
08/03/2005 ELECTRIC - INTERMEDIATE RSUBA Approved IVRS - Inspection :*
08/08/2005 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*
1) CORRECTION MADE
02/09/2006 U VALUE FOR WINDOW LHANLY Approved
07/27/2006 RIGHT OF WAY - FINAL NBRIGGS Approved
07/27/2006 ELECTRIC - TEMP POWER FOR TEST RSUBA Approved PER EL FINAL

Documents

File Name Document Type  
C OF O_08-04-2006.TIF CERT OF OCC VIEW
T04CM03061.PDF DOCUMENTS VIEW
None DOCUMENTS VIEW