Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2005 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* DAMPERS INSTALLED IN ROOM 339 ELECTRIC STILL TO BE TERMINATED ROOM 365 OK | |
| 07/01/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CEILING TILES IN MEDIA CENTER 2) OK TO CLOSE CEILING IN SCIENCE LABS |
|
| 06/24/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* RELOCATE DUCT SMOKE DETECTORS TO THE RETURN AIR DUCT. BE SURE TO USE A FULL LENGHT SENSING TUBE. SEAL AROUND FIRE DAMPER ANGLES. OK CEILING TILE RMS 350, 352, 353,359, 360, 362,363,364 | |
| 06/20/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES TEACHER'S WORK ROOM | |
| 06/10/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK FOR CEILING TILES BLDG 3 SCIENCE WING 2) STILL NEED TO SEE 2 FIRE/SMOKE DAMPERS IN ROOM 339 |
|
| 05/25/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CHECKED SUPPLY AND RETURN DUCTS IN CLASSROOMS 2) CHECKED CONDENSATE DRAIN LINES 3) OK FOR CEILING TILES ROOMS 335 THRU 338 |
|
| 05/24/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) INSPECTED SUPPLY AND RETURN IN ROOMS 303 THRU 312, 329 THRU 334 2) OK FOR CEILING TILES THESE ROOMS |