Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/08/2005 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :* DAMPERS INSTALLED IN ROOM 339 ELECTRIC STILL TO BE TERMINATED ROOM 365 OK
07/01/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK CEILING TILES IN MEDIA CENTER
2) OK TO CLOSE CEILING IN SCIENCE LABS
06/24/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :* RELOCATE DUCT SMOKE DETECTORS TO THE RETURN AIR DUCT. BE SURE TO USE A FULL LENGHT SENSING TUBE. SEAL AROUND FIRE DAMPER ANGLES. OK CEILING TILE RMS 350, 352, 353,359, 360, 362,363,364
06/20/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :* OK CEILING TILES TEACHER'S WORK ROOM
06/10/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK FOR CEILING TILES BLDG 3 SCIENCE WING
2) STILL NEED TO SEE 2 FIRE/SMOKE DAMPERS IN ROOM 339
05/25/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CHECKED SUPPLY AND RETURN DUCTS IN CLASSROOMS
2) CHECKED CONDENSATE DRAIN LINES
3) OK FOR CEILING TILES ROOMS 335 THRU 338
05/24/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) INSPECTED SUPPLY AND RETURN IN ROOMS 303 THRU 312, 329 THRU 334
2) OK FOR CEILING TILES THESE ROOMS