Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/21/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1) WATER TEST THRU ROOF WASTE AND VENT SCIENCE SECTION BLDG OK
2) BLDG 3 INTERMEDIATE-OK
3) 100 PSI TEST ALL OF BLDG 3 GAS PIPING OK
4) PARTIAL APPROVAL WAITING ON REVISED CITY APPROVED GAS ISOMETRIC
04/06/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :* WATER TEST & WASTE & VENT THRU ROOF ROOM J 363,357,358, 362,350,356,OK. H20 PIPING SAME AREAS OK. GAS PIPING FROM EAST METER THRU BUILDING TO ?? ROOFTOP UNITS, WATER HEATER & ADDED KILN 100 PSI TEST OK. PENDING REVISED CITY APPROVED PLAN OF GAS SYSTEM. PER HIGHLIGHTED INSTALLED PLAN IN TRAILER.
03/28/2005 PLUMBING - INTERMEDIATE Partial Approval H20 PIPING IN WALL RESTROOMS 326, 327, 322, 323, 314, 315
03/25/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WATER TREST WASTE AND VENT THRU ROOF PAGE 3 P1.1 AND H20 AND GAS PIPING OK
2) PAGE 3 P1.2 H20 OVERHEAD AND GAS OVERHEAD TO CUSTODIAL ROOM 313 OK
3) WASTE AND VENT THRU ROOF UNISEX 3221-323 OK PAGE 3 P1.1 WASTE AND VENT THRU ROO OK
4) H20 OVERHEAD OK
5) WASTE AND VENT THRU ROOF RESTROOM 314 AND 315; 326 AND 327 OK
6) ALL HIGH LIGHTED AND SIGNED IN TRAILER PLAN
01/19/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :* NORTH EAST WING 2 EWF WATER TEST 60 PSI & WASTER & VENT TO 8' WATER TEST OK