Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
5500 E 22ND ST
Address NEW:
5500 E 22ND ST
Apply Date:
05/21/2004
Applicant:
ARCHITECTURE WEST
Description:
TI:BAKERY
Architects:
  • DOMINGUEZ, PORFIRIO
Contractors:
  • GAD CONTRACTING L L C

Permit Reviews

Permit Number - T04CM02286
Permit Status: C of o
Permit Description: TI:BAKERY
Start Date Submittal Complete Date Status  
01/21/2005 3RD PARTY REVIEW-REVISION/OTHER 01/21/2005 COMPLETED Review Details
01/28/2005 3RD PARTY REVIEW-REVISION/OTHER 01/28/2005 COMPLETED Review Details
05/26/2004 PLANS OK TO SUBMIT - 3RD PARTY 05/27/2004 COMPLETED Review Details
05/27/2004 3RD PARTY REVIEW-COMMERCIAL TI 06/29/2004 COMPLETED Review Details
06/29/2004 POST 3RD PARTY REVIEW 08/23/2004 COMPLETED Review Details
09/22/2004 3RD PARTY REVIEW-REVISION/OTHER 09/23/2004 COMPLETED Review Details
10/18/2004 3RD PARTY REVIEW-REVISION/OTHER 10/19/2004 COMPLETED Review Details
12/08/2004 3RD PARTY REVIEW-REVISION/OTHER 12/09/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04CM02286
Permit Status: C of o
Permit Description: TI:BAKERY
Total Outstanding Activity Conditions - 1
Date Name
05/21/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T04CM02286
Permit Description: TI:BAKERY
Total Completed Inspections - 29
Date Description Inspector Results Comments
08/31/2004 ELECTRIC - INTERMEDIATE JORTA Approved IVRS - Inspection :*/ 1) CONDUIT ITEM #C, B, G APPROVED 2) PANEL BOARD BP APPROVED 3) PLEASE CALL WHEN ALL WALK ARE COMPLETE FOR INTERMEDIATE
08/31/2004 BUILDING PRE-SLAB HLEYVA Approved IVRS - Inspection :*
09/29/2004 PLUMBING - ROUGH, SOIL RRICH Approved IVRS - Inspection :*/WATER TEST WASTE & VENT THRU ROOF OK. H20 PIPING WATER TEST OK. REVISED CITY APPROVED PLAN ON SITE.
09/29/2004 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection :*
10/05/2004 BUILDING ABOVE CEILING LHANLY Approved IVRS - Inspection :*
10/05/2004 FRAMING LHANLY Approved IVRS - Inspection :*
10/05/2004 SHEET ROCK NAILING LHANLY Approved IVRS - Inspection :*
10/20/2004 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*/GREASE DUCT PLAN HAS BEEN REVISED-OK TO INSTALL 16X18 DUCTS. PLEASE PROVIDE A COMPLETE BALANCE REPORT ON FINAL INSPECTION
11/04/2004 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*/ENCLOSE THE BOTTOM OF THE SHAFTS AROUND THE GREASE DUCTS W/SHEET METAL. HAVE A STEP LADDER ON THE JOB TO INSPECT CONNECTIONS TO THE TOP OF THE HOOD FOR FINAL
11/12/2004 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*/CORRECTION MADE
11/12/2004 PLUMBING - GAS PRESS TEST FNL RRICH Approved IVRS - Inspection :*/15 PSI AIR TEST FROM METER TO APPLIANCES SHOWN PER APPROVED PLAN
11/12/2004 PLUMBING - GAS PRESSURE TEST RRICH Approved IVRS - Inspection :*
11/12/2004 PLUMBING - ABOVE CEILING RRICH Approved IVRS - Inspection :*
11/17/2004 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :
See detailed listing on site.| 999*/CONNECT THE WATER SUPPLY TO THE EVAP COOLERS. TYPE I EXSHAUST FAN MUST TERMINATE AT THE TOP OF THE WALL. PROVIDE A ROOF JACK ON ELEC. PENETRATION THRU THE ROOF. PROVIDE GREASE CUPS ON EXHAUST FANS & HOOD. NEED TO SEE BOTTOM OF SHAFT ENCLOSED WITH SHEET METAL. PROVIDE DRAIN ON EVAP COOLERS SEE DETAIL 101 SHEET M1.0. PROVIDE BALANCE REPORT ON EXHAUST FANS.
11/17/2004 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) OK TO CLEAR NEW SERVICE
2) INSTALL CORRECT LABELS ON BOTH SERVICES AS PER PLAN
3) JUMPER AT METER ENCLOSURE GROUND TO METAL
01/18/2005 FIRE - KITCHEN EXH HOOD FINAL LLAKEY Approved
01/24/2005 ELECTRIC - SERVICE RELOCATION RSUBA Approved
01/24/2005 ELECTRIC - CABLE DROP RSUBA Approved
01/24/2005 ELECTRIC - SERVICE UPGRADE RSUBA Approved
01/24/2005 ELECTRIC - UFER RSUBA Approved
01/24/2005 ENGINEERING - FINAL JSALINE Approved C OF O APPROVED.
01/24/2005 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
01/26/2005 RIGHT OF WAY - FINAL DLEE Approved
02/07/2005 FIRE SPKLR - FINAL LLAKEY Approved
02/10/2005 BUILDING - FINAL LHANLY Approved IVRS - Inspection :*AP OK C-OF-O
02/10/2005 FIRE - FINAL LLAKEY Approved
02/11/2005 SIGN INSPECTION JYBARRA Approved
02/11/2005 HEALTH DEPT - FINAL 724-7908 RPAYTON Approved
02/14/2005 PERMIT FINALED LJACKSON Approved