Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM02286
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/31/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* RE CALCULATED AIR VOLUMES ACCEPTED BY STANTEC FOR REVISED HOOD CALCULATIONS. STANTEC APP 1/27/05 | |
01/10/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*EXHAUST & MAKE UP AIR TEST RESULTS CAME UP BELOW DESIGN PARAMETERS. i WILL HAVE OUR PLANS EXAMINER CHECK RESULTS TO SEE IF THEY ARE ADEQUATE. | |
11/17/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/CONNECT THE WATER SUPPLY TO THE EVAP COOLERS. TYPE I EXSHAUST FAN MUST TERMINATE AT THE TOP OF THE WALL. PROVIDE A ROOF JACK ON ELEC. PENETRATION THRU THE ROOF. PROVIDE GREASE CUPS ON EXHAUST FANS & HOOD. NEED TO SEE BOTTOM OF SHAFT ENCLOSED WITH SHEET METAL. PROVIDE DRAIN ON EVAP COOLERS SEE DETAIL 101 SHEET M1.0. PROVIDE BALANCE REPORT ON EXHAUST FANS. |