Permit: T04CM02286


Addresses:

5500 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/31/2005 MECHANICAL - FINAL Approved IVRS - Inspection :* RE CALCULATED AIR VOLUMES ACCEPTED BY STANTEC FOR REVISED HOOD CALCULATIONS. STANTEC APP 1/27/05
01/10/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*EXHAUST & MAKE UP AIR TEST RESULTS CAME UP BELOW DESIGN PARAMETERS. i WILL HAVE OUR PLANS EXAMINER CHECK RESULTS TO SEE IF THEY ARE ADEQUATE.
11/17/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/CONNECT THE WATER SUPPLY TO THE EVAP COOLERS. TYPE I EXSHAUST FAN MUST TERMINATE AT THE TOP OF THE WALL. PROVIDE A ROOF JACK ON ELEC. PENETRATION THRU THE ROOF. PROVIDE GREASE CUPS ON EXHAUST FANS & HOOD. NEED TO SEE BOTTOM OF SHAFT ENCLOSED WITH SHEET METAL. PROVIDE DRAIN ON EVAP COOLERS SEE DETAIL 101 SHEET M1.0. PROVIDE BALANCE REPORT ON EXHAUST FANS.