Permit: T04CM02286


Addresses:

5500 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM02286

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/24/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*APPROVED
01/10/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*1) INSTALL BREAKERS PER PLAN OR REVISE PLANS ACCORDINGLY ( EXAMPLE CIRS. 8, 0, 12 S/B 25 AMP 3 POLE, CIRS. 14, 16, 18 S/B 3 POLE 20 AMP NOT 2 POLE 30, CIR. 30 NOT INDICATED ON PLAN. PLEASE REMOVE OR REVISE ACCORDINGLY, CIR. 29 NOT SHOWN ON PLAN, HOT CASE M-1 S/B 2 POLE 35 AMP BREAKER, SELF COMPENSATION HOOD S/B 3 POLE 40 AMP C BREAKER NOT 20 AMP TYPE PANEL SCHEDULE FOR CLARITY 2) PULL CIRCUITS PER PLAN OR REVISE PLANS. 3) TREAT PLYWOOD THAT SERVICE EQUIP IS MOUNTED ON. 4) JOB MUST REFLECT THE APPROVED PLANS CHECK ALL OF IT W/PLANS PRIOR TO MY NEXT INSPECTION.
11/17/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OK TO CLEAR NEW SERVICE
2) INSTALL CORRECT LABELS ON BOTH SERVICES AS PER PLAN
3) JUMPER AT METER ENCLOSURE GROUND TO METAL