Inspection History Details
Permit: T04CM02286
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2005 | MECHANICAL - INTERMEDIATE | Approved | ||
| 10/20/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/GREASE DUCT PLAN HAS BEEN REVISED-OK TO INSTALL 16X18 DUCTS. PLEASE PROVIDE A COMPLETE BALANCE REPORT ON FINAL INSPECTION | |
| 10/08/2004 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/16X18 GREASE DUCT IS NOT SIZED ADEQUATELY FOR THE EXHAUST FANS SPECIFIED ON PLANS. RE SUBMIT PLANS TO ENGINEER & HAVE SYSTEM REDESIGNED & APPROVED. THE ORIGINAL DISIGN WITH 28X28 DUCTS MAY NOT BE ADEQUATE EITHER. ANY QUESTIONS CONTACT BOB SHERRY CITY OF TUCSON @ 791-550 EXT. 2209 |
|
| 10/05/2004 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/GREASE DUCT NOT SIZED PER PLANS |