Permit: T04CM01434
Permit Details
Status:
C of o
Type:
COMMERCIAL ADDITION
Address:
6934 E TANQUE VERDE RD
Address NEW:
6934 E TANQUE VERDE RD
Apply Date:
03/26/2004
Applicant:
N/A
Description:
ADDITION:SHOWROOM/WAREHOUSE
Architects:
- GONZALEZ, RICKY LINN
Contractors:
- CIENAGA CANYON CONTRACTORS LLC
Permit Reviews
Permit Number - T04CM01434
Permit Status: C of o
Permit Description: ADDITION:SHOWROOM/WAREHOUSE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/03/2008 | POST 3RD PARTY REVIEW | 01/10/2008 | COMPLETED |
| 01/04/2008 | 3RD PARTY REVIEW-REVISION/OTHER | 01/04/2008 | COMPLETED |
| 03/15/2005 | 3RD PARTY REVIEW-REVISION/OTHER | 03/15/2005 | COMPLETED |
| 03/15/2005 | POST 3RD PARTY REVIEW | 03/15/2005 | COMPLETED |
| 03/26/2004 | PLANS OK TO SUBMIT - 3RD PARTY | 04/05/2004 | COMPLETED |
| 03/26/2004 | PLANS OK TO SUBMIT - SITE | 04/01/2004 | COMPLETED |
| 04/05/2004 | SITE | 04/30/2004 | COMPLETED |
| 04/05/2004 | 3RD PARTY REVIEW-COMMERCIAL | 04/12/2004 | COMPLETED |
| 05/13/2004 | 3RD PARTY REVIEW-COMMERCIAL | 05/13/2004 | COMPLETED |
| 05/13/2004 | POST 3RD PARTY REVIEW | 06/03/2004 | COMPLETED |
| 05/19/2004 | RESUBMITTAL - SITE | 06/03/2004 | COMPLETED |
| 06/17/2004 | RESUBMITTAL - SITE ALL | 07/23/2004 | COMPLETED |
| 06/17/2004 | RESUBMITTAL | 07/23/2004 | COMPLETED |
| 06/20/2008 | REVISION - SITE | 06/20/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04CM01434
Permit Status: C of o
Permit Description: ADDITION:SHOWROOM/WAREHOUSE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/26/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T04CM01434
Permit Description: ADDITION:SHOWROOM/WAREHOUSE
Total Completed Inspections - 43
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2005 | FRAMING | BSTEVENS | Approved | |
| 05/27/2005 | FRAMING | BSTEVENS | Approved | |
| 05/27/2005 | ROOF NAILING | BSTEVENS | Approved | |
| 05/27/2005 | ROOF NAILING | BSTEVENS | Approved | IVRS - Inspection :* |
| 07/27/2005 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :* 1) OK WALLS AT PORCH SUBJECT TO PLANS |
| 08/29/2005 | STUCCO MESH | LHANLY | Approved | IVRS - Inspection :* TOWER ON EXIST BLD OK (PORCH ALSO) |
| 10/02/2006 | ELECTRIC - UFER | RHOLLAND | Approved | IVRS - Inspection :* 1. BRACING IS REQUIRED BY MANUFACTURERS LABELING 2. PREVENT OBJECTIONABLE CURRENT -- 250.6 3. PROVIDE R PINS AND FUSE. |
| 10/03/2006 | ELECTRIC - CABLE DROP | RHOLLAND | Approved | IVRS - Inspection :* 1) NEED REJECTION PINS |
| 10/04/2006 | TEP CLEARANCE - AM | JWEATHER | Approved | CEC CLEARED PER R. HOLLANDER |
| 10/19/2006 | ELECTRIC - SERVICE RELOCATION | RSUBA | Approved | IVRS - Inspection :* |
| 10/20/2006 | ELECTRIC - CONSTRUCTION POWER | RSUBA | Approved | IVRS - Inspection :* OK TO CLEAR ECO |
| 10/20/2006 | ELECTRIC - UNDERGROUND | RSUBA | Approved | IVRS - Inspection :* ALL PVC ABOVE 18" FROM FINISHED GRADE WILL NEED CONCRETE COVER. |
| 10/20/2006 | TEP CLEARANCE - PM | JWEATHER | Approved | TEC CLEARED PER R. SUBA |
| 11/16/2006 | EXCAVATION/LAYOUT REBAR & ZON | JBURGE | Approved | IVRS - Inspection :* OK TO POUR FOOTINGS |
| 11/27/2006 | STEM WALL/RETAINING WALL | JBURGE | Approved | IVRS - Inspection :* FORMS IN PLACE -- OK TO POUR |
| 12/07/2006 | PLUMBING - ROUGH, SOIL | BBENEDON | Approved | IVRS - Inspection :* HAVE PLUMBER RED LINE CHANGES OK FOR CONCRETE |
| 12/28/2006 | REINFORCED MASONRY PRE-GROUT | JBURGE | Approved | RAINED OUT |
| 12/29/2006 | EXT METAL CLIPS/EXT SHEATHING | IVR USER | Approved | IVRS - AP canceled |
| 03/05/2007 | BUILDING PRE-SLAB | GDABBS | Approved | IVRS - Inspection :* PLUMBING PIPES WRAPPED |
| 04/05/2007 | BUILDING ABOVE CEILING | JBURGE | Approved | IVRS - Inspection :* |
| 04/17/2007 | PLUMBING - GAS PRESSURE TEST | BBENEDON | Approved | IVRS - Inspection :* |
| 04/17/2007 | PLUMBING - ABOVE CEILING | BBENEDON | Approved | IVRS - Inspection :* |
| 04/17/2007 | PLUMBING - INTERMEDIATE | BBENEDON | Approved | IVRS - Inspection :* |
| 05/03/2007 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* 3/8" I.D X 24 GAS FLEX NOT ADEQUATE FOR 96,000 BTU ADD EVAP. COOLERS & ANY RELATED TRADES OR ACTIVITIES TO PERMIT & PLANS. ALSO, REVICE A/C DUCTING ON PLANS SUPPORT WATER LINES TO COOLERS EVERY 6' |
| 05/03/2007 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* |
| 05/03/2007 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* |
| 05/03/2007 | ELECTRIC - ABOVE CEILING | CCLEMENS | Approved | IVRS - Inspection :* |
| 06/25/2007 | SHEET ROCK NAILING | JBURGE | Approved | IVRS - Inspection :* OK TO TAPE THROUGHOUT |
| 09/13/2007 | PLUMBING - YARD WTR LINE/TEST | BBENEDON | Approved | IVRS - Inspection :* INSTALLED PER REDLINE PROVIDE REVISION |
| 09/20/2007 | PLUMBING - SEWER HCS CONNECT | RLEDONNE | Approved | IVRS - Inspection :* |
| 03/11/2008 | U VALUE FOR WINDOW | JBURGE | Approved | IVRS - Inspection :* 2ND FLOOR 64 VALUE; 1ST 1/8" THERMAL TEMPERED SYSTEM |
| 03/11/2008 | BUILDING - PROGRESS | JBURGE | Approved | IVRS - Inspection :* |
| 03/13/2008 | PLUMBING - FINAL | BBENEDON | Approved | IVRS - Inspection :* |
| 03/14/2008 | OUTDOOR LIGHTING FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
| 03/14/2008 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
| 03/14/2008 | ELECTRIC - OUTDOOR LIGHTING | RHOLLAND | Approved | IVRS - Inspection :* |
| 03/14/2008 | ELECTRIC - RECONNECT | RHOLLAND | Approved | IVRS - Inspection :* |
| 03/19/2008 | BUILDING - FINAL | JBURGE | Approved | IVRS - Inspection :* OK TO OCCUPY |
| 03/19/2008 | RIGHT OF WAY - FINAL | PWHIDDON | Approved | PER EMAIL |
| 03/19/2008 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
| 03/19/2008 | LANDSCAPE - FINAL | ACONNOR | Approved | |
| 03/19/2008 | FIRE - FINAL | LTHOMAS | Approved | |
| 06/24/2008 | ENGINEERING - FINAL | JBRUCKME | Approved |