Permit: T04CM01434

Parcel: 133152920

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/14/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/11/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. DRYWALL SCREWS NOT FOR MOUNTING OF SERVICE EQUIPMENT
2. NEED ELECTRICIAN PRESENT TO OPEN SERVICE & PANELS
3. PANEL LABELING TO BE AS PER 408.4 NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER
4. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
5. OUTSIDE LIGHT NOT WORKING