Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
MULTI FAMILY NEW
Address NEW:
811 E WETMORE RD 03
Apply Date:
09/18/2003
Applicant:
N/A
Description:
NEW:APARTMENT BUILDING 3
Architects:
  • MORROW, KEVIN THOMAS
Contractors:
  • FINA COMPANIES L L C

Permit Reviews

Permit Number - T03CM04563
Permit Status: C of o
Permit Description: NEW:APARTMENT BUILDING 3
Start Date Submittal Complete Date Status  
02/14/2005 3RD PARTY REVIEW-REVISION/OTHER 03/01/2005 COMPLETED Review Details
05/18/2005 3RD PARTY REVIEW-REVISION/OTHER 10/31/2005 COMPLETED Review Details
07/28/2004 3RD PARTY REVIEW-COMMERCIAL 07/28/2004 COMPLETED Review Details
07/28/2004 POST 3RD PARTY REVIEW 08/03/2004 COMPLETED Review Details
08/07/2006 3RD PARTY REVIEW-REVISION/OTHER 08/18/2006 COMPLETED Review Details
09/09/2004 3RD PARTY REVIEW-REVISION/OTHER 09/09/2004 COMPLETED Review Details
09/18/2003 PLANS OK TO SUBMIT - 3RD PARTY 09/29/2003 COMPLETED Review Details
10/01/2003 3RD PARTY REVIEW-COMMERCIAL 10/23/2003 COMPLETED Review Details
11/09/2004 3RD PARTY REVIEW-REVISION/OTHER 12/23/2004 COMPLETED Review Details
11/26/2004 3RD PARTY REVIEW-COMMERCIAL 11/30/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T03CM04563
Permit Status: C of o
Permit Description: NEW:APARTMENT BUILDING 3
Total Outstanding Activity Conditions - 1
Date Name
09/18/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T03CM04563
Permit Description: NEW:APARTMENT BUILDING 3
Total Completed Inspections - 43
Date Description Inspector Results Comments
09/14/2004 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*/1)ABS DWV UNDERGROUND OK
PLUMBER SHOWED ME NOTATION ALLOWING 1% GRADE. WATER TEST ONE RISER TO TEN FEET-OK OK TO BACKFILL
09/15/2004 ELECTRIC - INTERMEDIATE MCAPISTR Approved IVRS - Inspection :*/ 1) UNDERGROUND PVC DATA AND COMM. USE OK
10/18/2004 EXCAVATION/LAYOUT REBAR & ZON AMATHIES Approved IVRS - Inspection :*
10/20/2004 ELECTRIC - UFER MCAPISTR Approved IVRS - Inspection :*/ONE LOCATION ON WEST END
11/05/2004 STEM WALL/RETAINING WALL AMATHIES Approved IVRS - Inspection :*
11/08/2004 BUILDING PRE-SLAB AMATHIES Approved IVRS - Inspection :*
12/03/2004 PLUMBING - SEWER HCS CONNECT RMYERS Approved IVRS - Inspection :*
12/09/2004 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
12/09/2004 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
12/10/2004 ELECTRIC - CABLE DROP MCAPISTR Approved IVRS - Inspection :*
12/28/2004 REINFORCED MASONRY PRE-GROUT AMATHIES Approved IVRS - Inspection :*
06/03/2005 ROOF NAILING AMATHIES Approved IVRS - Inspection :*
06/23/2005 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
1) PVC DWV ALL FIRE FLOORS OK. ? WATER ALL FIVE FLOORS OK. ? OK. CLOSET FLANGES OK
2) OK TO COVER ALL AREAS
06/23/2005 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :* 1) ROB BEGOODY CANCELLED VIA PHONE.
06/24/2005 PLUMBING - ROOF DRAINS RMYERS Approved IVRS - Inspection :* 1) ROOF DRAINS OK TO COVER. SCUPPER-NO OVERFLOW
06/28/2005 ELECTRIC - ABOVE CEILING MCAPISTR Approved IVRS - Inspection :*
07/05/2005 EXT METAL CLIPS/EXT SHEATHING AMATHIES Approved IVRS - Inspection :*
07/11/2005 U VALUE FOR WINDOW AMATHIES Approved IVRS - Inspection :*
07/21/2005 BUILDING ABOVE CEILING AMATHIES Approved IVRS - Inspection :*
07/29/2005 FRAMING AMATHIES Approved IVRS - Inspection :*
08/07/2005 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :*
1) 4TH FLOOR LOFT APTS., OK
08/08/2005 STUCCO MESH AMATHIES Approved IVRS - Inspection :*
08/17/2005 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
08/22/2005 RIGHT OF WAY - FINAL MOTERO Approved OK FOR TEMP C OF O - DEBBIE 4TH FLOOR
09/06/2005 SHEET ROCK NAILING AMATHIES Approved IVRS - Inspection :*
09/12/2005 TEP CLEARANCE - AM SLONG Approved ECO 3101-3110, 3201-3210, 3301-3310, 3401-3410
09/27/2005 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :*
10/03/2005 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :* YARDWATER PIPING AND CONNECTIONS AT BOTH ENDS OF THE BUILDING OK TO COVER
CONTRACTOR IS TO INSTALL AVB'S ON ALL HOSE BIBBS. ALL CONNECTIONS WITHOUT BACKFLOW PROTECTION TO BE REMOVED BEFORE FINAL
ALL EXTERIOR WALL PENETRATIONS TO BE SEALED.
10/03/2005 OUTDOOR LIGHTING FINAL RMAJUTA Approved IVRS - Inspection :* FIXTURES THRU OUT O/S BLD MISSING
FAR WEST ELECT RM NOT READY
LIGHTING CONTACTOR NOT INSTALLED
JUST NOT READY. HAVE ALL EMER LIGHTING ON FOR TESTING
10/03/2005 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*
10/04/2005 FIRE - FINAL LTHOMAS Approved
10/04/2005 FIRE - ALARM FINAL LTHOMAS Approved
10/04/2005 FIRE SPKLR - FINAL LTHOMAS Approved
10/04/2005 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
10/06/2005 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*CONTRACTOR TO RESOLVE ROOF DRAIN TERMINATION
PLUMBING FINAL OK.
OK FOR C OF O PENDING ANY OTHER INSPECTION.
10/07/2005 BUILDING - FINAL AMATHIES Approved IVRS - Inspection :* ok for temp C/O per A Mathieson
10/07/2005 NPPO - FINAL ACONNOR Approved Ok for Temp. C of O

Pending clean up of construction area, return visit on 10/10/05 may reverse result if site does not comply with previous comments.
10/07/2005 LANDSCAPE - FINAL ACONNOR Approved Ok for Temp. C of O

Pending clean up of construction area, return visit on 10/10/05 may reverse result if site does not comply with previous comments.
10/07/2005 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection :*
10/31/2005 ENGINEERING - FINAL MRUSSO Approved TEMP C OF O FOR ENGINEERING APPROVED, PERMANENT C OF O NOT TO BE GIVEN UNTIL ALL SITE WORK IS COMPLETED AND A FINAL GRADING INSPECTION FOR PERMIT # T03BU01928 IS COMPLETED AND APPROVED.
07/28/2006 PERMIT FINALED LJACKSON Approved
07/28/2006 MECHANICAL - ABOVE CEILING CWILLIAM Approved PER MECH FINAL
07/28/2006 ELECTRIC - UNDERGROUND RMAJUTA Approved PER EL FINAL

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CERT OF OCC VIEW