Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM04563
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/19/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPPORT NM CABLE WITHIN 12" OF BOXES, CANS AND FANS 2) PROTECT NM CABLE AT STUDS 3) OK 3RD FLOOR ROUGH AND 3405 ROUGH |
|
| 07/07/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/01/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 2ND FLOOR ROUGH-IN OK |
|
| 06/21/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1ST FLR. ROUGH IN COMPLETE. | |
| 06/20/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* MANY LOOSE ENDS-WTR HTR. CABLES LOOSE & OTHER SUCH PROBLEMS. | |
| 05/19/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ABOVE CEILING-PRE ROCK FLOORS 1 AND 2 |
|
| 01/24/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* HALLWAY ( BREEZEWAY) WALL LITES (J) BOXES IN ?? LOCK | |
| 01/21/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*RECALLED FOR MONDAY NOT READY | |
| 01/07/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PVC STUBS AT STAIR & ELEVATOR WELL. |
|
| 09/15/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) UNDERGROUND PVC DATA AND COMM. USE OK |