Inspection History Details
Inspection Status: Approved
Inspection History: OUTDOOR LIGHTING FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2006 | OUTDOOR LIGHTING FINAL | Approved | IVRS - Inspection :* | |
| 07/11/2006 | OUTDOOR LIGHTING FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOND ALL THESE SERVICES TO SAME GROUNDING ELECTRODE NEC 250.58 2. LEAVE UFER AND ONLY 2 GROUND RODS FOR GROUNDING ELECTRODE SYSTEM. 3. GROUND ELEVATOR DISCONNECT. 4. PROVIDE COMPANY LETTER DESCRIBING ALL ELECTRICAL PROBLEMS AND WHAT ACTION WAS TAKEN TO REMEDY IT. |
|
| 10/03/2005 | OUTDOOR LIGHTING FINAL | Not ready for Inspection | IVRS - Inspection :* FIXTURES THRU OUT O/S BLD MISSING FAR WEST ELECT RM NOT READY LIGHTING CONTACTOR NOT INSTALLED JUST NOT READY. HAVE ALL EMER LIGHTING ON FOR TESTING |