Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Apply Date:
08/27/2003
Applicant:
N/A
Description:
TI:RESTAURANT
Architects:
  • KENYON, DAVID LLOYD
Contractors:
  • SUNG S CONSTRUCTION L L C

Permit Reviews

Permit Number - T03CM04234
Permit Status: C of o
Permit Description: TI:RESTAURANT
Start Date Submittal Complete Date Status  
01/07/2004 REVISION 01/07/2004 COMPLETED Review Details
01/28/2004 REVISION 01/29/2004 COMPLETED Review Details
01/29/2004 REVISION 02/06/2004 COMPLETED Review Details
02/06/2004 REVISION 02/06/2004 COMPLETED Review Details
08/27/2003 PLANS OK TO SUBMIT - COMM 08/28/2003 COMPLETED Review Details
08/28/2003 COMMERCIAL NEW 09/24/2003 COMPLETED Review Details
10/09/2003 RESUBMITTAL 11/06/2003 COMPLETED Review Details
11/06/2003 RESUBMITTAL 11/19/2003 COMPLETED Review Details
11/19/2003 REVISION 11/20/2003 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T03CM04234
Permit Status: C of o
Permit Description: TI:RESTAURANT
Total Outstanding Activity Conditions - 1
Date Name
08/27/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T03CM04234
Permit Description: TI:RESTAURANT
Total Completed Inspections - 29
Date Description Inspector Results Comments
11/20/2003 ELECTRIC - UNDERGROUND RSUBA Approved SUSHI BAR, WAITRESS STATION, KITCHEN EQUIP, BAR
11/24/2003 FRAMING RSUBA Approved IVRS - Inspection 0000* RECALL WHEN OTHER WALLS FRAMED
12/05/2003 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection 0000*/ 1) PLEASE PROVIDE A LETTER AUTHORIZING USE OF M/C CABLE AND FLEX CONDUIT 2) OK WALLS SUBJECT TO LETTER
12/09/2003 PLUMBING - GAS PRESS TEST FNL RMYERS Approved IVRS - Inspection 0000*
12/11/2003 SHEET ROCK NAILING AMATHIES Approved IVRS - Inspection 0000*
12/15/2003 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection 0999*/ INSULATE ALL GREASE DUCT FROM POINT OF CEILING PENETRATION TO THE OUTLET TERMINAL. SEE SEC. 506.3.11 NOTE #1 - 2000 IMC. INSULATE ALL BARE METAL DUCT ON SUPPLY AND RETURN. INSPECTED CONDENSATE DRAIN LINES.
12/15/2003 PLUMBING - ROUGH, SOIL JSTANLEY Approved IVRS - Inspection 0000*/ PLEASE PROVIDE APPROVED REVISED PLAN BY NEXT INSP.
12/17/2003 MECHANICAL - HOODS JMILITEL Approved IVRS - Inspection 0000*/ INSPECTED FIRE WRAP ON GREASE DUCTS. INSPECTED ALL DUCT ABOVE CEILING. COMPLETE WIRING DUCT SMOKE DETECTORS TO BE DONE BY ELECTRICIAN. LEAVE OUT A CEILING TILE UNDER EACH DUCT SMOKE DETECTOR.
12/17/2003 PLUMBING - INTERMEDIATE JSTANLEY Approved IVRS - Inspection 0000*/ ROOM 106 OK TO COVER. PLEASE PROVIDE APPROVED REVISED PLAN FOR HAND SINK AND CALL FOR INTERMEDIATE. ALSO COMPLETE HANGER AS PER LAST REQUEST AND CALL FOR ABOVE CEILING
12/31/2003 ELECTRIC - ABOVE CEILING RHOLLAND Approved IVRS - Inspection 0000*/ 1) A SUPPORT WIRE PER CAN IS NEEDED 2) SUPPORT M/C CABLE WITHIN 12" OF CANS 3) SUPPORT WIRES FOR 2 X 4 FIXTURE NEEDED
01/09/2004 PLUMBING - ABOVE CEILING TRINIVJR Approved IVRS - Inspection 0000*/ APPROVED DRAWING IS ON SITE. 2) ABOVE CEILING IS OK FOR GRID AND TILE.
01/14/2004 BUILDING - TEMP POWER FOR TEST RSUBA Approved IVRS - Inspection 0000*
01/15/2004 MECHANICAL - TEMP PWR FOR TEST JMILITEL Approved IVRS - Inspection 0000*/ NOTE: EF-1 AND 5 MUST BE EXTENDED TO DISCHARGE NO LOWER THAN THE TOP OF THE PARRAPET WALL.
01/22/2004 PLUMBING - TEMP POWER FOR TEST TRINIVJR Approved
01/22/2004 ELECTRIC - TEMP POWER FOR TEST MCAPISTR Approved
02/12/2004 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection 0000*/ OK FOR FINAL C OF O.
02/12/2004 MECHANICAL - PROGRESS JMILITEL Approved
02/12/2004 MECHANICAL - INTERMEDIATE JMILITEL Approved
02/12/2004 RIGHT OF WAY - FINAL PWHIDDON Approved
02/12/2004 PLUMBING - FINAL JSTANLEY Approved IVRS - Inspection 0000*
02/12/2004 PLUMBING - PROGRESS JSTANLEY Approved
02/12/2004 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection 0000*/ OK FINAL.
02/12/2004 BUILDING - FINAL LHANLY Approved IVRS - Inspection 0000*
02/13/2004 HEALTH DEPT - FINAL 724-7908 DTHOMAS Approved
02/13/2004 ENGINEERING - FINAL JSALINE Approved
02/13/2004 FIRE SPKLR - FINAL LTHOMAS Approved
02/18/2004 FIRE - FINAL LLAKEY Approved IVRS - Inspection 0000*
02/18/2004 FIRE - KITCHEN EXH HOOD FINAL LLAKEY Approved IVRS - Inspection 0000*
02/19/2004 SIGN - FINAL JYBARRA Approved IVRS - Inspection 0000*

Documents

File Name Document Type  
None DOCUMENTS VIEW
C OF O_02-20-2004.TIF CERT OF OCC VIEW