Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM04234
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/12/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ OK FOR FINAL C OF O. | |
02/11/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ EXTEND SEWER VENTS 2' ABOVE EVAP COOLERS. PROVIDE OUTSIDE AIR INTAKES ON A/C UNITS. PERMANENTLY LABEL ALL EQUIPMENT ON ROOF WITH SUITE NO. AND UNIT NO. [EF-1, AC-1, ETC.] PROVIDE A TRAP ON CONDENSATE DRAIN FOR WALK IN COOLER. RECALL FOR FINAL INSPECTION. IT'S OK FOR A C OF O. |