Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM04234

Parcel: 11004345C


Addresses:

3305 N SWAN RD #111


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM04234

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/12/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ OK FOR FINAL C OF O.
02/11/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ EXTEND SEWER VENTS 2' ABOVE EVAP COOLERS. PROVIDE OUTSIDE AIR INTAKES ON A/C UNITS. PERMANENTLY LABEL ALL EQUIPMENT ON ROOF WITH SUITE NO. AND UNIT NO. [EF-1, AC-1, ETC.] PROVIDE A TRAP ON CONDENSATE DRAIN FOR WALK IN COOLER. RECALL FOR FINAL INSPECTION. IT'S OK FOR A C OF O.