Permit: T03CM04234

Parcel: 11004345C


Addresses:

3305 N SWAN RD #111


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T03CM04234

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/12/2004 MECHANICAL - ABOVE CEILING Approved
12/15/2003 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*/ INSULATE ALL GREASE DUCT FROM POINT OF CEILING PENETRATION TO THE OUTLET TERMINAL. SEE SEC. 506.3.11 NOTE #1 - 2000 IMC. INSULATE ALL BARE METAL DUCT ON SUPPLY AND RETURN. INSPECTED CONDENSATE DRAIN LINES.