Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T03CM04234
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/12/2004 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* | |
12/15/2003 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000*/ PLEASE PROVIDE APPROVED REVISED PLAN BY NEXT INSP. | |
12/02/2003 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ INTERCEPTOR INSTALLED OK. CLEANOUTS INSTALLED AS REQUIRED. OK TO BACKFILL. | |
12/01/2003 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999* AGGREGATE CHANGE OF DIRECTION CANNOT EXCEED 135 DEGREE WITHOUT ADDITIONAL CLEAN OUT. | |
11/19/2003 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 1) VENTED CSST UNDERSLAB INSTALLED PER PLAN. PLEASE HAVE THE REVISED PLAN APPROVED BY THE CITY. 2) OK TO BACKFILL SUBJECT TO REVISED PLAN. | |
11/13/2003 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 1) ABS DWV UNDERGROUND OK. WATER TEST ONE RISER TO TEN FEET. 2) NEED TO SEE GREASE TRAP INSTALLATION. 3) OK TO COVER. |