Permit: T03CM01876
Permit Details
Status:
C of o
Type:
COMMERCIAL ADDITION
Address:
500 W SAINT MARYS RD
Address NEW:
500 W SAINT MARYS RD
Apply Date:
04/16/2003
Applicant:
HEERY INTERNATIONAL INC *C
Description:
ADDITION:PHYSICAL EDUCATION BLDG & EXPAND:KITCHEN
Architects:
- TOM, RICHARD FE
Contractors:
- CORONA SIERRA INC ,
- TUCSON UNIFIED SCHOOL DIST #1
Permit Reviews
Permit Number - T03CM01876
Permit Status: C of o
Permit Description: ADDITION:PHYSICAL EDUCATION BLDG & EXPAND:KITCHEN
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/12/2005 | RESUBMITTAL | 01/21/2005 | COMPLETED |
| 04/06/2004 | PLANS OK TO SUBMIT - SITE | 10/14/2004 | COMPLETED |
| 04/16/2003 | PLANS OK TO SUBMIT - COMM | 05/08/2003 | COMPLETED |
| 05/08/2003 | COMMERCIAL NEW | 06/12/2003 | COMPLETED |
| 07/29/2005 | REVISION | 07/30/2005 | COMPLETED |
| 09/26/2003 | RESUBMITTAL | 12/08/2003 | COMPLETED |
| 10/14/2004 | RESUBMITTAL | 11/24/2004 | COMPLETED |
| 10/26/2005 | REVISION | 10/26/2005 | COMPLETED |
| 10/26/2005 | REVISION | 12/06/2005 | COMPLETED |
| 11/24/2004 | RESUBMITTAL | 01/04/2005 | COMPLETED |
| 11/24/2004 | RESUBMITTAL - SITE | 01/04/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T03CM01876
Permit Status: C of o
Permit Description: ADDITION:PHYSICAL EDUCATION BLDG & EXPAND:KITCHEN
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/16/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T03CM01876
Permit Description: ADDITION:PHYSICAL EDUCATION BLDG & EXPAND:KITCHEN
Total Completed Inspections - 40
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2005 | ELECTRIC - UFER | RMAJUTA | Approved | IVRS - Inspection :* #2 SOL LOPPER UFER 20' + |
| 03/09/2005 | EXCAVATION/LAYOUT REBAR & ZON | HLEYVA | Approved | IVRS - Inspection :* OK @ MAIN BLDG |
| 03/14/2005 | STEM WALL/RETAINING WALL | AQUIROZ | Approved | IVRS - Inspection :* |
| 04/08/2005 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :* 1) ABAS DWV UNDERGROUND OK WATER TEST ONE RISER TO TEN FEET OK OK TO COVER |
| 04/13/2005 | BUILDING PRE-SLAB | HLEYVA | Approved | IVRS - Inspection :* OK @ MAIN BLDG |
| 04/25/2005 | ELECTRIC - TEMPORARY SERVICE | MCAPISTR | Approved | IVRS - Inspection :* TEMP POLE-WEST END OF CONST TRLR |
| 04/26/2005 | TEP CLEARANCE - AM | JKOZUCH | Approved | TEMP POLE FOR CONSTRUCTION |
| 07/01/2005 | ELECTRIC - INTERMEDIATE | MCAPISTR | Approved | IVRS - Inspection :* 1) GYM MAIN FLOOR WALLS-PIPE, BOXES AND RINGS-NO WIRE |
| 07/06/2005 | ROOF NAILING | AMATHIES | Approved | IVRS - Inspection :* |
| 07/08/2005 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection :* |
| 07/14/2005 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* MISSING BLOCKING FOR ADA IN RESTROOMS, AND WINDOW FRAMING |
| 07/19/2005 | PLUMBING - GAS PRESSURE TEST | RRICH | Approved | IVRS - Inspection :* 1) 1 1/4 FROM METER WITH 1/2" STUB 6" ABOVE MAIN IN CEILING SPACE AT NORTH EAST END 1 1/4 CONTINOUS UP TO CEILING SPACE NORTH EAST OF BIG ROOM AND IS CAPPED. 20 PSI TEST PARTIAL APPROVAL 2) AT PENETRATION OF TOP PLATE OF BEARING WALL FOR GAS PIPE TOP PLATE IS OVER NOTCHED AND WILL REQUIRE INSPECTION BY BLDG INSPECTOR FOR REPAIR FOR ENGINEERS SPECS. DO NOT COVER THIS |
| 07/19/2005 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection :* 1) WATER TEST WASTE AND VENT THRU ROOF OK 2) H20 PIPING 100 PSI TEST OK 3) FINISH INSTALL OF TRAP PRIMER AND DISTRIBUTION DEVICE. PROVIDE VIEWING AT FINAL |
| 08/16/2005 | SHEET ROCK NAILING | AMATHIES | Approved | IVRS - Inspection :* |
| 08/16/2005 | STUCCO MESH | AMATHIES | Approved | IVRS - Inspection :* |
| 10/14/2005 | PLUMBING - YARD WTR LINE/TEST | RMYERS | Approved | IVRS - Inspection :* 1) SPEC CALLS FOR COPPER YARD WATER 2) INSTALLED IS SCHEDULE 40 PVC FROM FENCE LINE TO STUB UP AT BLDG OK TO COVER SUBJECT TO ARCHITECT APPROVAL |
| 12/19/2005 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
| 12/19/2005 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
| 12/19/2005 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 12/19/2005 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 12/19/2005 | FIRE - FINAL | LTHOMAS | Approved | |
| 12/22/2005 | PLUMBING - SEWER HCS CONNECT | RMYERS | Approved | IVRS - Inspection :* NOT INSTALLED PER PLAN. REDLINES ON SITE OK TO COVER SUBJECT TO REVISED APPROVAL PLAN |
| 01/20/2006 | RIGHT OF WAY - FINAL | MOTERO | Approved | PER EMAIL |
| 01/20/2006 | PLUMBING - FINAL | TRINIVJR | Approved | |
| 01/20/2006 | PLUMBING - BACK WATER VALVE | TRINIVJR | Approved | |
| 01/20/2006 | PLUMBING - PROGRESS | TRINIVJR | Approved | IVRS - Inspection :* 1. PLUMBING FINAL IS OK 2. OK FOR C OF O |
| 01/20/2006 | PLUMBING - GAS PRESS TEST FNL | TRINIVJR | Approved | IVRS - Inspection :* |
| 01/20/2006 | PLUMBING - ABOVE CEILING | TRINIVJR | Approved | IVRS - Inspection :* |
| 01/20/2006 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection :* |
| 01/20/2006 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
| 03/07/2006 | MECHANICAL - FINAL | CWILLIAM | Approved | IVRS - Inspection :* |
| 03/07/2006 | MECHANICAL - ABOVE CEILING | CWILLIAM | Approved | IVRS - Inspection :* |
| 03/15/2006 | ENGINEERING - FINAL | MRUSSO | Approved | |
| 03/23/2006 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* |
| 03/23/2006 | U VALUE FOR WINDOW | AQUIROZ | Approved | IVRS - Inspection :* |
| 03/29/2006 | ELECTRIC - ABOVE CEILING | RMAJUTA | Approved | |
| 03/29/2006 | BUILDING ABOVE CEILING | AQUIROZ | Approved | |
| 03/29/2006 | MECHANICAL - INTERMEDIATE | CWILLIAM | Approved | |
| 03/29/2006 | MECHANICAL - PROGRESS | CWILLIAM | Approved | |
| 04/05/2006 | PERMIT FINALED | LJACKSON | Approved |