Permit Number: T03CM01876
Parcel: 116162350

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM01876
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2003 GERRY KOZIOL WWM REVIEW Denied See previous comments
10/01/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Resize vent for P-3 and P-2 to comply with Table 7-4 Footnote 3, UPC 1994.
2. Provide vent piping of sufficient size to comply with Section 904.1, UPC.
3. Show size of scuppers on the drawing. (only the height of the scupper is shown on detail 4/A2.4BN). Reference Appendix D, UPC. Note: no provisions for overflows for the roof are evident on the plans.
10/01/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved 1. Resize vent for P-3 and P-2 to comply with Table 7-4 Footnote 3, UPC 1994.
2. Provide vent piping of sufficient size to comply with Section 904.1, UPC.
3. Show size of scuppers on the drawing. (only the height of the scupper is shown on detail 4/A2.4BN). Reference Appendix D, UPC. Note: no provisions for overflows for the roof are evident on the plans.
10/17/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. MPR does not reflect the required fixtures per Table 2902.1 IBC. Note: A total fixture count and occupant load of the school may be used if the total is in compliance with Table 2902.1 IBC. Note: May not use TUSD Enrollment numbers. Utilize Table 1003.2.2.2 IBC
10/20/2003 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Floodplain Use Permit Application - Davis School
REVIEWER: Doug Williams
DATE: 22 October 2003
ACTIVITY NUMBER(s): T03OT00811/T03CM01876

SUMMARY: Engineering Section has reviewed the Site plan, Grading Site Plan and Floodplain Use Permit application received on October 20, 2003. A grading permit will be required for this development. Please complete and submit a grading permit application with resubmittal of the above-referenced activity number permit applications. Please ensure 2 copies of the drainage report are included in the resubmittal. Approval is not recommended at this time - resubmittal is required. The following comments must be addressed:

SITE PLAN COMMENTS (Sheet AO.1DS):

1. Dimension and label the existing and future (Major Streets and Routes - MS&R Plan), rights-of-way to include intersection widening dimensioning for Granada Avenue at Saint Mary's Road (DS 2-02.2.1.19);
2. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways and utility lines (DS 2-02.2.21);

GRADING SITE PLAN (Sheet AO.2DS):

See summary regarding requirement for completion of a grading permit application. The following comments are preliminary in nature - further comments may be necessary upon grading permit application review.

1. Provide general excavation and grading notes - excavation and grading requirements may be accessed at: http://www.ci.tucson.az.us/dsd/2000_IBC_Amendments.pdf
2. Depict limits of grading. Proposed grading must meet setback requirements listed in Section 14 of the 2000 International Building Code - local amendment (above), and may not go beyond property lines without providing written permission from the affected property owner;
3. Provide bases of bearing and elevation;
4. Depict and label existing property lines;
5. Provide total area to be disturbed;

Note: The consultant and contractor should ensure interim erosion control measures such as silt fencing and/or hay bales are instituted during construction, for stormwater pollution prevention purposes.

If you have any questions, I can be reached at 791-5550, ext. 1189 or Dwillia1@ci.tucson.az.us

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
10/21/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
10/21/2003
See comments under T03CM01875

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2003 TAMI ACHONG OUT TO CUSTOMER Completed
12/05/2003 ANGIE SHOFFSTALL REJECT SHELF Completed