Permit: T03CM01876

Parcel: 116162350

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/23/2006 BUILDING - FINAL Approved IVRS - Inspection :*
03/06/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. THRESHOLDS MUST MEET ACCESSIBILITY REQUIREMENTS.
2. CLOSERS FOR DOORS NOT COMPLETE
3. ACCESSIBLE SIGNAGE NOT INSTALLED
4. YOUR PLAN SHOWS 9'10" CLEAR FLOOR SPACE IN GIRLS RESTROOM YOU ONLY HAVE 9'6". YOU NEED TO PROVIDE A DIMENSIONED AS BUILT FOR RESTROOMS WITH PARTITIONS YOU DO NOT SEEM TO BE COMPLYING WITH REQUIRED CLEAR FLOOR SPACE.