Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address NEW:
4355 S SANTA RITA AV
Apply Date:
08/06/2002
Applicant:
SONORAN EXPEDITING
Description:
TI:MANUFACTURING BUILDING
Contractors:
  • HAZEN LTD , STEVE

Permit Reviews

Permit Number - T02CM03689
Permit Status: C of o
Permit Description: TI:MANUFACTURING BUILDING
Start Date Submittal Complete Date Status  
04/28/2003 3RD PARTY REVIEW-REVISION/OTHER 05/02/2003 COMPLETED Review Details
08/06/2002 3RD PARTY COMMERCIAL TI 08/19/2002 COMPLETED Review Details
09/24/2002 REVISION 09/26/2002 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T02CM03689
Permit Status: C of o
Permit Description: TI:MANUFACTURING BUILDING
Total Outstanding Activity Conditions - 1
Date Name
08/06/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T02CM03689
Permit Description: TI:MANUFACTURING BUILDING
Total Completed Inspections - 24
Date Description Inspector Results Comments
08/29/2002 ELECTRIC - UNDERGROUND RMAJUTA Approved IVRS - Inspection 0000*OK TO COVER 2-4" PVC'S TEP TRANSFORMER. TO CT CAN CONCRETE ENCLOSE LAST 4-5' INTO TRANSFORMER.
09/26/2002 SHEET ROCK NAILING LHANLY Approved IVRS - Inspection 0000*
09/30/2002 PLUMBING - TEMP POWER FOR TEST RMYERS Approved IVRS - Inspection 0000*1.) CONTRACTOR IS REQUESTING TEMP C OF O. 2.) TENANT HAS AMPLE EXISTING FACILITIES TO ACCOMODATE NECESSARY USAGE. THREE BATHROOMS. 3.) OK WITH PLUMBING INSPECTOR FOR TEMP C OF O. PENDING REVIEW BY S. LONG.
09/30/2002 BUILDING - TEMP POWER FOR TEST LHANLY Approved IVRS - Inspection 0000*FOR NEW EQUIP. BAYS ONLY.
10/01/2002 PERMIT FINALED JYBARRA Approved
10/01/2002 RIGHT OF WAY - FINAL LLOPEZ Approved
10/01/2002 SIGN - FINAL JYBARRA Approved NO SIGNS AT THIS TIME
10/01/2002 ENGINEERING - FINAL JBRUCKME Approved
10/01/2002 FIRE - FINAL LTHOMAS Approved OK FOR TEMP C OF O FOR TEMP POWER IN NEW PANELS
10/01/2002 FIRE SPKLR - FINAL LTHOMAS Approved
10/01/2002 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection 0000*
10/01/2002 MECHANICAL - TEMP PWR FOR TEST CWILLIAM Approved IVRS - Inspection 0000*
10/01/2002 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection 0000*
10/01/2002 ELECTRIC - TEMP POWER FOR TEST JORTA Approved
12/19/2002 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection 0999*
1.) APPEAR THAT INSTALLATION NO LONGER REFLECTS APPROVED PLAN PROVIDE ACCURATE AS BUILTS AS INSTALLED.
2.) 400A PNLS F & E NEED TO BE 22,000 RATED
3.) NEW LATHE'S & MILLS JAPAN ARE NOT LISTED
4.) PANEL SCHEDULES DO NOT REFLECT ACTUAL INSTALLATION AS BUILTS TO REFLECT CHANGES.
LISTINGS REQUIRED PER NEC 110-3 PLEASE PROVIDE A LISTING FOR ALL UNLISTED EQUIPMENT AMERICAN OR FORIENG.
12/19/2002 ELECTRIC - CABLE DROP RMAJUTA Approved IVRS - Inspection 0000*
12/19/2002 ELECTRIC - ABOVE CEILING RMAJUTA Approved IVRS - Inspection 0000*
12/19/2002 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection 0000*
12/19/2002 BUILDING - FINAL LHANLY Approved IVRS - Inspection 0999*1.) PROVIDE FINALS FROM OTHER TRADES.
2.) EGRESS ROUTES NEED TO COMPLY WITH ADA GUIDE LINES IE NO TWISTING OF KIND TO GET OUT.
3.) LOCK ON APA ROUTE MUST UNLOCK AUTOMATICALLY FROM EGRESS SIDE (ADA RESTROOM).
4.) ADA SIGNAGE TO BE 60" FROM FLOOR & MOUNTED ON WALL ON LATCH SIDE. ADA SIGNAGE SHOULD INCLUDE BRAILLE.
12/19/2002 BUILDING ABOVE CEILING LHANLY Approved IVRS - Inspection 0000*
12/19/2002 FRAMING LHANLY Approved IVRS - Inspection 0000*
12/20/2002 PLUMBING - FINAL RMYERS Approved IVRS - Inspection 0000*
1.) CORRECTIONS MADE OK
2.) INSPECTOR SATISFIELD CONCERNING PREVIOUS INSPECTIONS.
3.) OK FOR C OF O PENDING ANY OTHER INSPECTION.
12/20/2002 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection 0000*
12/20/2002 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection 0000*

Documents

File Name Document Type  
T02CM03689 2025 MASS-UPLOAD.PDF DOCUMENTS VIEW
None CERT OF OCC VIEW