Permit: T02CM03689

Parcel: 13217136A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/06/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK C OF O.
01/31/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES
1.) AS BUILDS NEED TO BE STAMPED AND APPROVED BY C.O.T. PLAN CHECK
2.) EQUIP. NEED TO BE LISTED PER CERTIFIED ELECTRICAL ENGINEER.
12/19/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) APPEAR THAT INSTALLATION NO LONGER REFLECTS APPROVED PLAN PROVIDE ACCURATE AS BUILTS AS INSTALLED.
2.) 400A PNLS F & E NEED TO BE 22,000 RATED
3.) NEW LATHE'S & MILLS JAPAN ARE NOT LISTED
4.) PANEL SCHEDULES DO NOT REFLECT ACTUAL INSTALLATION AS BUILTS TO REFLECT CHANGES.
LISTINGS REQUIRED PER NEC 110-3 PLEASE PROVIDE A LISTING FOR ALL UNLISTED EQUIPMENT AMERICAN OR FORIENG.
10/04/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
10/04/2002 ELECTRIC - FINAL Partial Approval TEMP C OF O..
09/26/2002 ELECTRIC - FINAL Partial Approval SERVICE APPROVED: 4355 'E' AND 'F' TEMP C OF O APPROVED SUBJECT TO OTHER INSPECTOR. WILL NEED LETTER FROM LICENSED CONTRACTOR STATING THAT SAID COMPANY IN DOING THE ELECTRIC WORK AND HOOK UP. EQUIPMENT TO BE INSTALLED IN INCREMENTS OF DAYS AND TO BE USED AS COMPLETED NOTE WILDAN REVISION ATTACHED.
09/19/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*IMPROPERLY SIZED BONDING JUMPER AN SUPPLY SIDE RISERS AD MAIN BONDING JUMPER. SHOULD BE 3/0 AWG MIN. NEED CITY APPROVED LETTER AND REFERENCE TO SAME KEY NOTE AND INSERT ACTIVITY NUMBER. A REFEE IS DUE BEFORE THE NEXT.
09/13/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999* NEED ACCURATE CITY APPROVED REVISION FOR ONE LINE DIAGRAM. SHOW ALL WIRE SIGN GROUND ELECTRODE SYSTEM NEED PROPERTY SIZED BOND. JUMPER & MAIN BOND JUMPER.