Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T01CM01468
Permit Details
Apply Date:
03/27/2001
Applicant:
NICK KRAUJA, AIA
Description:
FUELING FACILITY
Architects:
- ULRICH, ROGER LANE
Contractors:
- ASHTON COMPANY INC CONTRACTORS A
Permit Reviews
Permit Number - T01CM01468
Permit Status: Expired
Permit Description: FUELING FACILITY
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
02/12/2003 | RESUBMITTAL | 11/14/2003 | COMPLETED |
03/08/2002 | RESUBMITTAL | 07/02/2002 | COMPLETED |
03/08/2002 | SITE | 04/18/2002 | COMPLETED |
03/27/2001 | SITE | 04/25/2001 | COMPLETED |
04/25/2001 | COMMERCIAL NEW | 05/31/2001 | COMPLETED |
04/25/2001 | SITE | 05/31/2001 | COMPLETED |
04/28/2004 | REVISION | 04/28/2004 | COMPLETED |
04/28/2004 | REVISION | 05/27/2004 | COMPLETED |
05/15/2002 | SITE | 11/19/2003 | COMPLETED |
06/07/2004 | RESUBMITTAL | 06/08/2004 | COMPLETED |
06/18/2001 | RESUBMITTAL | 08/08/2001 | COMPLETED |
06/18/2001 | COMMERCIAL NEW | 07/30/2001 | COMPLETED |
08/08/2001 | RESUBMITTAL | 02/06/2002 | COMPLETED |
08/09/2001 | SITE | 02/06/2002 | COMPLETED |
10/09/2001 | REVISION | 02/06/2002 | COMPLETED |
11/25/2002 | RESUBMITTAL | 12/02/2003 | COMPLETED |
12/05/2003 | RESUBMITTAL | 12/18/2003 | COMPLETED |
12/20/2002 | REVISION | 02/12/2003 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01CM01468
Permit Status: Expired
Permit Description: FUELING FACILITY
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
03/27/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01CM01468
Permite Description: FUELING FACILITY
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2009 | PLUMBING - FINAL | N/A | Denied | 1) PROVIDE APPROVED PLAN AND INSPECTION HISTORY 2) PROVIDE VERIFICATION OF STERILIZATION 3) PROVIDE CLEAN BACTERIA REPORT 4) PROVIDE COPY OF AUTHORITY TO DISCHARGE 5) CONTINUED NOT READYS MAY RESULT IN A REINSPECTION FEE |
Completed Inspections
Permit Status: Expired
Permit Number: T01CM01468
Permit Description: FUELING FACILITY
Total Completed Inspections - 34
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/06/2004 | PLUMBING - YARD WTR LINE/TEST | RMYERS | Approved | IVRS - Inspection :*/ 1) 2" WTR SERVICE FROM SUNTRAN FUELING BLDG TO METER LOCATION. 2" TYPE 'L' WITH COMP. CAUP. CONNECTIONS OK. I QUESTION THE USE OF A GALVENIZED RISER ON A PREDOMINENTLY COPPER SYSTEM. ALSO 2" COPPER WTR LINE FOR FUTURE BLDG INSTALLED MINUS THE RPA. 2) OK TO COVER. I NEED TO SEE BACKFLOW DEVICES AND CERTS FOR FINAL. |
09/15/2004 | ELECTRIC - FINAL | RMAJUTA | Approved | 1) METER FOR STREET LIGHTS 2) NEED AND ADDRESS ON OUTSIDE OF UNIT 3) NEED A GROUND BUSING BELOW METER UNPROTECTED CONDUCTORS 3) TIE NEUTRAL GROUND ELECTRODE CONDUCTOR COMING OF RODS 5) THERE MAYBE AN ADDRESS PROBLEM ONCE CLEARANCE GIVEN, ADDRESS 3990 N. SUNTRAN BLVD. |
09/24/2004 | ELECTRIC - UFER | RMAJUTA | Approved | IVRS - Inspection :* |
10/12/2004 | STEM WALL/RETAINING WALL | HLEYVA | Approved | IVRS - Inspection :* |
10/27/2004 | ELECTRIC - UNDERGROUND | MCAPISTR | Approved | OK TO BACKFILL FUEL ISLAND & ROOM 108 & 108A OK TO CLEAR METER SET FOR 3990 N SUN TRAN BL |
11/01/2004 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :*/1)CONTRACTOR: POST YOUR ADDRESS!! 2)YOU MAY WANT TO REVIEW YOUR INSPECTION HISTORY AND BRING 03055, 03040 UP TO DATE, 3)N/H WITH HUSKEE BANDS DWV UNDERGROUND OK. WATER TEST OK 4)3" STORM DRAIN STABBED OUT OF BLDG AND TO ABOVE GRADE IN 2 PLACES OK. OK TO COVER. 3" STORM DRAIN OK TO COVER |
11/04/2004 | ELECTRIC - INTERMEDIATE | MCAPISTR | Approved | IVRS - Inspection :*.1) INSTALLATION OF 13.8 KV GEAR APPROVED. 2) OK TO SUBMIT CLEARANCE TO TEP ( TO METER AND ENERGIZE HI VOLT PRIMARY) |
11/05/2004 | TEP CLEARANCE - AM | JKOZUCH | Approved | PER BETH COMPANY MUST POST BY MONDAY OR CLEARANCE MAY BE REVERSED |
12/06/2004 | BUILDING PRE-SLAB | AQUIROZ | Approved | IVRS - Inspection :*/ 1) ISLAND PAD |
12/10/2004 | EXCAVATION/LAYOUT REBAR & ZON | AQUIROZ | Approved | IVRS - Inspection :* 1) PIPE SUPPORT FOOTING OK |
12/29/2004 | REINFORCED MASONRY PRE-GROUT | AQUIROZ | Approved | IVRS - Inspection :* 1) 4TH LIFT |
02/08/2005 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* |
02/09/2005 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :*APPROVED FOR 3960 AND 3990 |
02/09/2005 | ROOF NAILING | AQUIROZ | Approved | IVRS - Inspection :*APPROVED FOR 3960 AND 3990 |
02/27/2005 | MECHANICAL - INTERMEDIATE | CWILLIAM | Approved | IVRS - Inspection :* PARTIAL OK TO COVER REST RM. CEILING |
03/09/2005 | ELECTRIC - TEMPORARY POLE | RMAJUTA | Approved | IVRS - Inspection :* |
04/29/2005 | PLUMBING - PROGRESS | RMYERS | Approved | IVRS - Inspection :* |
04/29/2005 | PLUMBING - ABOVE CEILING | RMYERS | Approved | IVRS - Inspection :* |
05/03/2005 | OUTDOOR LIGHTING FINAL | MCAPISTR | Approved | IVRS - Inspection :* |
05/03/2005 | ELECTRIC - ABOVE CEILING | MCAPISTR | Approved | IVRS - Inspection :* |
05/04/2005 | FIRE - HYDRANTS | CSCHULTZ | Approved | |
05/10/2005 | PLUMBING - BACK WATER VALVE | RMYERS | Approved | IVRS - Inspection :* |
05/26/2005 | MECHANICAL - FINAL | CWILLIAM | Approved | IVRS - Inspection :* |
06/03/2005 | PLUMBING - SEWER HCS CONNECT | RMYERS | Approved | IVRS - Inspection :* |
02/21/2006 | NPPO - FINAL | ACONNOR | Approved | |
02/21/2006 | LANDSCAPE - FINAL | ACONNOR | Approved | |
02/21/2006 | NPPO - FINAL | ACONNOR | Approved | |
02/21/2006 | LANDSCAPE - FINAL | ACONNOR | Approved | |
03/12/2008 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* AS DIRECTED PER JESSE SANDERS |
03/12/2008 | FIRE - FINAL | LLAKEY | Approved | |
03/12/2008 | SIGN - FINAL | JYBARRA | Approved | |
03/13/2008 | ENGINEERING - FINAL | MRUSSO | Approved | |
03/14/2008 | RIGHT OF WAY - FINAL | MOTERO | Approved | PER EMAIL |
06/09/2008 | PERMIT FINALED | GBONILLA | Approved |