Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL NEW
Apply Date:
03/27/2001
Applicant:
NICK KRAUJA, AIA
Description:
FUELING FACILITY
Architects:
  • ULRICH, ROGER LANE
Contractors:
  • ASHTON COMPANY INC CONTRACTORS A

Permit Reviews

Permit Number - T01CM01468
Permit Status: Expired
Permit Description: FUELING FACILITY
Start Date Submittal Complete Date Status  
02/12/2003 RESUBMITTAL 11/14/2003 COMPLETED Review Details
03/08/2002 RESUBMITTAL 07/02/2002 COMPLETED Review Details
03/08/2002 SITE 04/18/2002 COMPLETED Review Details
03/27/2001 SITE 04/25/2001 COMPLETED Review Details
04/25/2001 COMMERCIAL NEW 05/31/2001 COMPLETED Review Details
04/25/2001 SITE 05/31/2001 COMPLETED Review Details
04/28/2004 REVISION 04/28/2004 COMPLETED Review Details
04/28/2004 REVISION 05/27/2004 COMPLETED Review Details
05/15/2002 SITE 11/19/2003 COMPLETED Review Details
06/07/2004 RESUBMITTAL 06/08/2004 COMPLETED Review Details
06/18/2001 RESUBMITTAL 08/08/2001 COMPLETED Review Details
06/18/2001 COMMERCIAL NEW 07/30/2001 COMPLETED Review Details
08/08/2001 RESUBMITTAL 02/06/2002 COMPLETED Review Details
08/09/2001 SITE 02/06/2002 COMPLETED Review Details
10/09/2001 REVISION 02/06/2002 COMPLETED Review Details
11/25/2002 RESUBMITTAL 12/02/2003 COMPLETED Review Details
12/05/2003 RESUBMITTAL 12/18/2003 COMPLETED Review Details
12/20/2002 REVISION 02/12/2003 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T01CM01468
Permit Status: Expired
Permit Description: FUELING FACILITY
Total Outstanding Activity Conditions - 1
Date Name
03/27/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01CM01468
Permite Description: FUELING FACILITY
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
10/06/2009 PLUMBING - FINAL N/A Denied 1) PROVIDE APPROVED PLAN AND INSPECTION HISTORY
2) PROVIDE VERIFICATION OF STERILIZATION
3) PROVIDE CLEAN BACTERIA REPORT
4) PROVIDE COPY OF AUTHORITY TO DISCHARGE
5) CONTINUED NOT READYS MAY RESULT IN A REINSPECTION FEE

Completed Inspections

Permit Status: Expired
Permit Number: T01CM01468
Permit Description: FUELING FACILITY
Total Completed Inspections - 34
Date Description Inspector Results Comments
05/06/2004 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*/ 1) 2" WTR SERVICE FROM SUNTRAN FUELING BLDG TO METER LOCATION. 2" TYPE 'L' WITH COMP. CAUP. CONNECTIONS OK. I QUESTION THE USE OF A GALVENIZED RISER ON A PREDOMINENTLY COPPER SYSTEM. ALSO 2" COPPER WTR LINE FOR FUTURE BLDG INSTALLED MINUS THE RPA. 2) OK TO COVER. I NEED TO SEE BACKFLOW DEVICES AND CERTS FOR FINAL.
09/15/2004 ELECTRIC - FINAL RMAJUTA Approved 1) METER FOR STREET LIGHTS 2) NEED AND ADDRESS ON OUTSIDE OF UNIT 3) NEED A GROUND BUSING BELOW METER UNPROTECTED CONDUCTORS 3) TIE NEUTRAL GROUND ELECTRODE CONDUCTOR COMING OF RODS 5) THERE MAYBE AN ADDRESS PROBLEM ONCE CLEARANCE GIVEN, ADDRESS 3990 N. SUNTRAN BLVD.
09/24/2004 ELECTRIC - UFER RMAJUTA Approved IVRS - Inspection :*
10/12/2004 STEM WALL/RETAINING WALL HLEYVA Approved IVRS - Inspection :*
10/27/2004 ELECTRIC - UNDERGROUND MCAPISTR Approved OK TO BACKFILL FUEL ISLAND & ROOM 108 & 108A
OK TO CLEAR METER SET FOR 3990 N SUN TRAN BL
11/01/2004 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*/1)CONTRACTOR: POST YOUR ADDRESS!! 2)YOU MAY WANT TO REVIEW YOUR INSPECTION HISTORY AND BRING 03055, 03040 UP TO DATE, 3)N/H WITH HUSKEE BANDS DWV UNDERGROUND OK. WATER TEST OK 4)3" STORM DRAIN STABBED OUT OF BLDG AND TO ABOVE GRADE IN 2 PLACES OK. OK TO COVER. 3" STORM DRAIN OK TO COVER
11/04/2004 ELECTRIC - INTERMEDIATE MCAPISTR Approved IVRS - Inspection :*.1) INSTALLATION OF 13.8 KV GEAR APPROVED. 2) OK TO SUBMIT CLEARANCE TO TEP ( TO METER AND ENERGIZE HI VOLT PRIMARY)
11/05/2004 TEP CLEARANCE - AM JKOZUCH Approved PER BETH COMPANY MUST POST BY MONDAY OR CLEARANCE MAY BE REVERSED
12/06/2004 BUILDING PRE-SLAB AQUIROZ Approved IVRS - Inspection :*/ 1) ISLAND PAD
12/10/2004 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection :*
1) PIPE SUPPORT FOOTING OK
12/29/2004 REINFORCED MASONRY PRE-GROUT AQUIROZ Approved IVRS - Inspection :*
1) 4TH LIFT
02/08/2005 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
02/09/2005 FRAMING AQUIROZ Approved IVRS - Inspection :*APPROVED FOR 3960 AND 3990
02/09/2005 ROOF NAILING AQUIROZ Approved IVRS - Inspection :*APPROVED FOR 3960 AND 3990
02/27/2005 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :* PARTIAL OK TO COVER REST RM. CEILING
03/09/2005 ELECTRIC - TEMPORARY POLE RMAJUTA Approved IVRS - Inspection :*
04/29/2005 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection :*
04/29/2005 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
05/03/2005 OUTDOOR LIGHTING FINAL MCAPISTR Approved IVRS - Inspection :*
05/03/2005 ELECTRIC - ABOVE CEILING MCAPISTR Approved IVRS - Inspection :*
05/04/2005 FIRE - HYDRANTS CSCHULTZ Approved
05/10/2005 PLUMBING - BACK WATER VALVE RMYERS Approved IVRS - Inspection :*
05/26/2005 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :*
06/03/2005 PLUMBING - SEWER HCS CONNECT RMYERS Approved IVRS - Inspection :*
02/21/2006 NPPO - FINAL ACONNOR Approved
02/21/2006 LANDSCAPE - FINAL ACONNOR Approved
02/21/2006 NPPO - FINAL ACONNOR Approved
02/21/2006 LANDSCAPE - FINAL ACONNOR Approved
03/12/2008 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
AS DIRECTED PER JESSE SANDERS
03/12/2008 FIRE - FINAL LLAKEY Approved
03/12/2008 SIGN - FINAL JYBARRA Approved
03/13/2008 ENGINEERING - FINAL MRUSSO Approved
03/14/2008 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL
06/09/2008 PERMIT FINALED GBONILLA Approved

Documents

File Name Document Type  
SPECIALINSPRPT_01.TIF DOCUMENTS VIEW
SPECIALINSPRPT_02.TIF DOCUMENTS VIEW
None DOCUMENTS VIEW