Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/04/2005 |
ELECTRIC - FINAL |
|
Approved |
|
| 05/03/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 09/15/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |