Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 04/29/2005 |
PLUMBING - PROGRESS |
|
Approved |
IVRS - Inspection :* |
| 04/08/2005 |
PLUMBING - PROGRESS |
|
Not ready for Inspection |
IVRS - Inspection :* DIELECTRIC UNION MAY NOT BE INSTALLED UNDERGROUND. RELOCATE METER TO CORRECT POSITION AND ELIMINATE BYPASS. INSTALL ALL PIPING MAKE ALL CONNECTIONS THERE ARE STILL UNRESOLVED PROGRESS NOTES 01/09/04 02/07/05 |
| 02/07/2005 |
PLUMBING - PROGRESS |
|
Partial Approval |
IVRS - Inspection :* 1) ROOF DRAINS AT ISLAND OK TO ROOF NO DRAIN INSTALLED. 2) OK TO COVER ALL AREAS |
| 01/09/2004 |
PLUMBING - PROGRESS |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) 8" DIP FROM MH#1 (PUBLIC) TO MH #2 INSTALLED OK; SUBJECT TO VERIFICATION OF GRADE AND AIR TEST AT A LATER DATE. NO BASES SET. OK TO COVER (PHASE TWO) 8" SDR 35 STUB FOR FUTURE OK |