Inspection Status: Partial Pass
Inspection History: COT - LCPL - Yard Water Line
| Date |
Description |
Inspector |
Results |
Comments |
| 08/26/2026 |
COT - LCPL - Yard Water Line |
|
Partial Pass |
Main water line trench 4" IPS high density polyethylene was already backfilled, verified depth and tracer via pictures from contractor, was also holding 105 psi of air. |
| 09/01/2026 |
COT - LCPL - Yard Water Line |
|
Partial Pass |
9/1/26: 4" processed water drain pipe/cleanout verified under test at 110psi. Okay to backfill progress areas using shading materials. |